2.1
Proportional directional spool valve type PSLF, PSVF, and SLF
according to the Load-Sensing principle
size 3 and 5 (manifold mounting)
D 7700-F
Prop. directional spool
valve PSLF, PSVF and SLF
HAWE HYDRAULIK SE
STREITFELDSTR. 25 • 81673 MÜNCHEN
© 1998 by HAWE Hydraulik
August 2011-05
1. General information
The directional spool valves types PSLF and PSVF as well
as the individual sections type SLF serve to control both, the
direction of movement and the load-independent, stepless
velocity of the hydraulic consumers. In this way several
consumers may be moved simultaneously, independently
from each other at different velocity and pressure ratings, as
long as the sum of the partial flows needed for this is within
the total delivery supplied by the pump.
The proportional spool valves of this pamphlet are designed
as manifold mounting valves. They may be also combined
as valve banks via the sub-plates available from HAWE.
They consist of three functional groups.
Basic data
Design Prop. directional spool valve according to the
Load-Sensing principle
Versions Individual valves and valve banks
(manifold mounting)
Operating pressure p
max
420 bar
Flow Q
max
80 (120) lpm (size 3)
Q
max
160 (240) lpm (size 5)
Further technical information:
Size Design Pamphlet
2 Manifold mounting design D 7700-2
2 Valve bank design (CAN onboard) D 7700 CAN
3 Valve bank design D 7700-3
5 Valve bank design D 7700-5
7 Manifold mounting design D 7700-7F
Mounting
; Inlet section(control section)
< Size 5 (valve bank design)
= End plate
> Sub-plates
1. General information ...................................... 1
2. Type coding, overview .................................. 2
3. Available version, main data ........................ 4
3.1 Connection blocks and end plates .................................... 4
3.2 Add-on spool valves .......................................................... 9
4. Characteristic data ...................................... 18
4.1 General and hydraulic ...................................................... 18
4.2 Curves .............................................................................. 19
4.3 Actuations ......................................................................... 20
4.4 Functional cut-off, prop. pressure limitation ..................... 24
4.5 Other solenoid valves ....................................................... 24
5. Unit dimensions ........................................... 25
5.1 Size 3 ............................................................................... 25
5.2 Size 5 ............................................................................. 39
6. Appendix ...................................................... 55
6.1 Notes for selection and lay-out ........................................ 55
6.2 Circuit examples ............................................................... 59
6.3 Notes regarding assembly, installation and conversion .... 59
Table of contents
<
;
=
>
D 7700-F page 2
2. Type coding, overview
Valve section (for individual orders, without sub-plate) Inlet section (for individual order, without sub-plate)
SLF 3 - A2 J 25/16 C300 / EA - G 24
PSLF A H1 F80 / 400 - 3 - G 24
Order examples:
Valve bank
PSLF A H1 F80 / 400 /4 - 3 - A2 J 25/16 C300 /EA /3 AN320 BN320
- A2 O 80/63 F1 /EA /3 - E4 - G 24
; Basic type coding for the valve bank or inlet section (see
table 1 and 4 in sect. 3.1.1 and 3.1.2) as well as valve sections
(see sect. 3.2.1)
PSLF A Supply with pressurized oil by means of fixed
pump (open center)
PSVF A Supply with pressurized oil by means of
variable displacement pump (closed
center) with a delivery flow controller, or as a
second, separate unit if both valve banks are
connected to a constant pressure system
SLF Individual valve section, without sub-plate
< Additional elements (acc. to table 2 and 5 in sect. 3.1.1)
(no coding) Basic version
S, W Additional damping device in gallery LS
(only with PSVF, standard with PSLF)
B, B 4 ... B 7 Orifice in gallery LS (PSVF only)
G Restrictor check valve (type PSLF)
H Raised circulation pressure of the 3-way flow
controller (approx. 14 bar with type PSLF)
= Control oil supply (acc. to table 7, sect. 3.1.3)
(no coding) Without pressure reducing valve in case of an
external control oil supply (min. 20 bar up to
max. 40 bar)
1 With integrated pressure reducing valve for the
internal supply of control oil (control pressure
approx. 20 bar)
2 With integrated pressure reducing valve for the
internal supply of control oil (control pressure
approx. 40 bar)
> Optional 2/2-way solenoid valve for arbitrary idle pump
circulation (acc. to table 8, sect. 3.1.3)
(no coding) Without directional valve, but prepared for
retrofitting
F, Z, ZM = idle pump circulation when
valve is de-energized
D, V = idle pump circulation when
valve is energized
F.. or D.. When a pressure is specified, with pressure
limiting valve which can be activated as a
second pressure stage (e.g. F 50)
PA, PB, PD Prop. pressure limiting valve, with various
pressure ranges
? Pressure limiting valve (main pressure limitation) in the inlet
section (acc. to table 9, sect. 3.1.3)
(no coding) Without pressure limiting valve
(type PSVF only)
/ ... Pressure limiting valve factory set to ... bar
@ Sub-plate for the inlet section (acc. to table 3, sect. 3.1.1)
/4, /UNF 4 Size 3, standard (tapped ports for P and R
G 3/4 ISO 228/1 (BSPP) or 1 1/16-12
UN-2B SAE J 514)
/6 Size 5, standard (tapped ports for P and R
G 1 1/4 ISO 228/1 (BSPP))
/UNF 6 Size 5, standard (ports P and R 1 5/8-12
UN-2B SAE J 514)
/7 SAE Size 5 (flange SAE 1 1/2” 6000 psi)
A Size (acc. to table 1 and 5, sect. 3.1)
3 or 5 Various connection hole pattern (adapter
plates enabling direct mounting between
size 5 and 3 with type ZPL 53 acc. to table
10, sect. 3.1.4)
B Valve section - Basic function (acc. to table 13, section 3.2.1)
A 2 (standard) Spool valve with inflow controller for each
consumer
A 1 Spool valve without inflow controller, suitable
for consumers, which are actuated individu-
ally and successively but not simultaneously
(no additional functions possible)
A 5, A 7, AA 9 Inflow controller with enforced spring for
higher flow
A 8 4/3-way directional spool valve (pre-selector
valve)
AR 2, AR 5, like A 2, A 5, A 7 but with check valve function
AR 7
AX Blanking plate
C Coding for the flow-pattern (acc. to table 14, sect. 3.2.1 and 6 c)
L, M, F, H, J, B, R, O, P, A, Q, K, T, I, Y, Z, V, G, W, X
D Flow coding for port A and B (acc. to table 15, sect. 3.2.1)
.../... Coding for port A or B (independently
selectable)
3, 6, 10, 16, 25, 40, 63, 80 (size 3)
16, 25, 40, 63, 80, 120, 160 (size 5)
E LS-pressure limitation (deviating from the main pressure
setting, lower pressure for the connected consumer) no shock
valves (acc. to table 16 and 18, section 3.2.1) (doesn‘t apply
to spool valve types without inflow controller, coding A 1
B or
table 12)
(no coding) No secondary pressure limitation
A..., B... Only for consumer port or B
A...B... For consumer ports A and B
C... Joint for consumer port A and B
(not in conjunction with coding F.. or S. F )
De-energized
closed
De-energized
open
JGFEDCBA ?>=; JA; <
+
JI
H
GFE
D
C
BA@?>=<;
D 7700-F page 3
F Functional cut-off (acc. to table 17 and 18, sect. 3.2.1)
(doesn‘t apply to spool valve types without inflow controller,
coding A1 B or table 13)
(no coding) No functional cut-off
F 1 Electrical cut-off, consumer port A
F 2 Electrical cut-off, consumer port B
F 3 Electrical cut-off, consumer port A and B
FP 1(2, 3) Like F 1(2,3), however with electro-proportio-
nal pressure limitation
FPH 1(2, 3) Like FP 1(2,3), however with additional push-
button for manual emergency actuation
S, S 1 External hydraulic load signal pick-up from the
control signal port U (consumer port A) and W
(consumer port B)
G Types of actuation (acc. to table 19 and 20, sect. 3.2.1)
/A Manual actuation
/E Electro-hydraulic actuation
/EI Like /E however without stroke limita-
tion
/EA Electro-hydraulic and manual actuation
/E0A Like /EA, however without actuation
solenoid (prepared for retrofitting)
/H, /F Hydraulic actuation
/H UNF, /F UNF Like /H, /F however with port thread
7/16-20 UNF-2B SAE-4 (conf.
SAE J 514)
/HA, /FA Hydraulic, (solenoid) and manual
actuation
/HA UNF, /FA UNF Like /HA, /FA however with port
thread 7/16-20 UNF-2B SAE-4 (conf.
SAE J 514)
/HEA, /FEA Hydraulic and electric actuation
/HEA UNF, /FEA UNF Like /HEA, /FEA however with port
thread 7/16-20 UNF-2B SAE-4 (conf.
SAE J 514)
/C, /AR Detent (stepless), 3-step detent
/E0C, /E0AR Like /C, /AR however without actuati-
on solenoid (prepared for retrofitting)
/ER, /EAR Electrical , 3-step detent
/P Pneumatic actuation
/PA Pneumatic and manual actuation
/... Suffix 1 without hand lever
2 short lever
G Reinforced version (size 3)
N, N1 Proximity switch
V, VA, VB, VC, Contact switch monitoring
VCHO, VCHC the spool elevation
WA, WA-EX Position sensor
U Lift monitoring
(side indication)
H Sub-plate for the individual valve section (acc. to table 21,
section 3.2.2)
/3, /4, Size 3
/UNF 3, /UNF 4
/3 X, /4 X, Size3, joint load signal pick-up
/UNF 3 X, /UNF 4 W via port X
/38 Sub-plate size 3 for preselector
function
/3 AN.. BN.. Size 3, shock and suction valves at A
/UNF 3 AN.. BN.. and B together with pressure
specification
/3 AN.., /3 BN.., Size 3, shock and suction valves at A
/UNF 3 AN.., or B together with pressure
/UNF 3 BN.. specification
/3 A..B.. Size 3, shock valve at A and B
together with pressure specification
/3 A.., /3 B.. Size 3, shock valve at A or B
together with pressure specification
/U 3 Sub-plate size 3, for mounting of
ancillary blocks or for valve bank
design acc. to D 7700-3
/5, /UNF 5 Size 5
/5 S Size 5, with load signal pick-up from
control signal port U (consumer port A)
and W (consumer port B)
/53, 533, 534, Sub-plate size 5, prepared to accept
/UNF 534 valve sections size 3
/58 Sub-plate size 5, for preselector
function
/5 X, /UNF 5 X Size 5, joint load signal pick-up via
port X
/U 5, /U 53 Sub-plate size 5, for mounting of
ancillary blocks for valve bank design
acc. to D 7700-5 or D 7700-3
/5 SAE Sub-plate size 5, ports A and B with
flange SAE 1” (6000 psi)
/5 SAE S, /5 SAE 8 Size 5, see /5 S or /58, ports A, B
with flange SAE 1” (6000 psi)
/6 D SAE Size 5, double sub-plate,
ports A, B with flange SAE 1 1/4”
(6000 psi)
/Z AN..BN.. Size 5, intermediate plate with shock
and suction valves
I End plates (acc. to table 11, section 3.1.4)
E 1, E 1 SAE With T-port for control oil return
externally to the tank (basic type)
E 2, E 2 SAE Like E 1, with additional port Y for
connection to the LS-port of a fur-
ther, separately located PSV spool
valve (total number of the sequential
add-on valves 12)
E 3 Like E 1, with additional 3/2-way
directional solenoid valve for arbitra-
ry shut-off of pump circulation during
idle position of the valve spools
E 4, E 4 SAE Like E 1, however internal control oil
return, max. pressure 10 bar!
E 5, E 5 SAE Like E 2, however internal control oil
return, max. pressure 10 bar!
E 6 Like E 3, however internal control oil
return, max. pressure 10 bar!
E 7, E 8, E 9, E 10 Like E 1, E 2, E 4 or E 5 but with
additional return port
ZPL 53, ZPL 5 SAE 3 Adapter plates enabling direct moun-
ting of directional spool valves size 5
and 3
J Solenoid voltage and version (acc. to table 10, sect. 3.1.3)
G 12.. 12V DC, connection conf. EN 175 301-803 A
G 24.. 24V DC, connection conf. EN 175 301-803 A
G 24 EX 24V DC, explosion-proof version, acc. to
ATEX
G 24 EX 70 24V DC, explosion-proof version, acc. to
ATEX (ambient temperature 70°C)
G 24 MSHA 24V DC, explosion-proof version, acc. to
MSHA
G 24 EX 24V DC, explosion-proof version
G 24 TEX 70 24V DC, explosion-proof version
(ambient temperature 70°C)
G 24 MSHA 24V DC, fire-damp protected (mining)
G 24 M2FP 24V DC, fire-damp protected (mining)
(Australia)
G 12 IS 12V DC, explosion-proof version, fire-damp
protected (mining), intrinsically safe acc. to
ATEX (I M2 Ex d ib I)
AMP 12 K 4 12V DC, connection via AMP Junior Timer
AMP 24 K 4 24V DC, connection via AMP Junior Timer
S 12.. 12V DC, electr. connection via quarter turn plug
S 24.. 24V DC, electr. connection via quarter turn plug
DT 12 12V DC electr. connection via plug
Co. DEUTSCH
DT 24 24V DC electr. connection via plug
Co. DEUTSCH
D 7700-F page 4
There are two basic variations of connection blocks:
o Connection blocks with integrated 3-way flow controller, suitable for a fixed pump system (open-center) -type PSLF (see sect. 3.1.1)
o Connection blocks suited for a variable displacement pump system (closed center), a constant pressure systems, or if a
second or more separately located directional spool valve banks are fed in parallel - type PSVF (see sect. 3.1.2).
Order coding for an inlet section as individual section (examples): PSLF A1 F/250 - 3 - G 24
(Attention: Size specification absolutely necessary - 3 or -5) PSVF A2/300 - 5
3.1.1 Inlet sections for fixed pump systems (with integrated 3-way flow controller) type PSLF
Order examples:
PSLF A 1F/300 /4 - 3 -...-E1 - G 24 (valve bank)
PSLF A H 1F/300 - 3 - G 24 (individual section)
Table 10Table 1
Table 1: Basic type and size
Table 3: Coding of the sub-plate for the inlet sections
Type PSLF...-5 can be converted any time for use with
variable displacement pumps (similar to type PSVF AS..-5),
see sect. 6.3.3.
Symbols
PSLF A(H)../..-3
PSLF A(H)W../..-3
PSLF A(H)../..-5
PSLF A(H)W../..-5
Coding and
size
PSLF A ..-3
PSLF A ..-5
Max. pump delivery flow
(lpm)
approx. 100
approx. 350
Descrip-
tion
Individual
section
Coding
/4
/UNF 4
/6
/UNF 6
/7 SAE
Size
3
3
5
5
5
Ports ISO 228/1 (BSPP)
or SAE 514 J
P and R LS, M, T and Z
G 3/4 G 1/4
1 1/16-12 UN-2B 7/16-20 UNF-2B
G 1 1/4 G 1/4
1 5/8-12 UN-2B 7/16-20 UNF-2B
SAE 1 1/2” G 1/4
(6000 psi)
Basic type and additional elements
(acc. to table 1 and 2)
3. Available versions, main data
3.1 Inlet section (control section)
Note: Sub-plates with SAE-flange must not be com-
bined with sub-plates featuring tapped ports
(e.g. /5 S)
Sub-plates (acc. to table 3)
Table 2
Table 2: Coding for additional elements for notes and
descriptions, see sect. 6.1 a)
Coding Description
no coding Standard Integrated combination of orifice, check
valve, pre-load valve (pre-load pressure
approx. 25 bar).
W Like standard, but with increased throttle effect
G Restrictor check valve (without sequence valve),
increased throttling effect
H
Coding for 3-way flow controller with increased cir-
culation pressure (see sect. 4.2). Intended for valve
spools with increased flow (coding A 5 acc. to table
15), pre-selector spool valve (coding A 8 table 13).
T
Only available for type PSLF A..-3
Provision for locking the 3-way flow controller to
enable use with variable pump systems.
PSLF A../../4-3
PSLF A../../UNF 4-3
PSLF A../../6-5
PSLF A../../7 SAE-5
PSLF AG../..-3
PSLF AG../..-5
Additional elements
(acc. to table 2)
These additional elements are
illustrated in flow pattern sym-
bols of size 3, they do apply to
size 5 in the same way.
D 7700-F page 5
Symbols
Table 4: Basic type and size
Type PSLF...-5 can be converted any time for use with
variable displacement pumps (similar to type PSVF
AS..-5), see sect. 6.3.3.
Coding and
size
PSVF A ..-3
PSVF A ..-5
Max. pump delivery flow
(lpm)
approx. 100
approx. 350
Descrip-
tion
Individual
section
Basic type (acc. to table 5)
Sub-plates (acc. to table 3)
Additional elements (acc. to table 5)
These additional elements are illustrated
in flow pattern symbols of size 3, they do
apply to size 5 in the same way.
3.1.2 Inlet sections for variable displacement pump systems / constant pressure system or for a second and all other
separately parallel connected directional spool valve banks type PSVF
Order examples:
Nom. voltage acc. to table 10
PSVF A 1F/300 /6 - 5 -...-E1 - G 24 (valve bank)
PSVF A B/250 - 3 (individual section)
Sub-plate acc. to table 3, sect. 3.1.1
Table 5: Code letter for features within the LS-signal duct for
the damping of pump flow controllers (for notes and
explanation, see sect. 6.1 a)
Additional features only suitable where variable
displacement pumps are used (limitation of the control
oil flow). Observe note at table 8!
Coding Description
no coding Standard, without additional element
S
With integrated combination of orifice, check
valve, pre-load valve (pre-load pressure approx.
25 bar) like standard element of type PSLF
W
Like S, but with increased throttle effect
B
With orifice # 0.8 mm within LS-duct (limiting the
control oil flow)
B 4, B 5,
B 6, B 7
With orifice # 0.4 mm, 0.5 mm, 0.6 mm or 0.7 mm
within LS-duct
PSVF A../..-3 PSVF A../..-5
PSVF A../4-3
PSVF A../UNF 4-3
PSVF A../6-5
PSVF A../7 SAE-5
PSVF AS...-3
PSVF AS...-5
PSVF AB...-3
PSVF AB...-5
D 7700-F page 6
3.1.3 Additional elements for the inlet sections
Order examples:
PSLF A.
1F100 /380/4 - 3 -...- E1 - G24
PSVF A. 1F /350 -5 - G24
Symbols
Coding Description
no coding
/...
Version without pressure limiting valve (only type
PSVF)
With pressure limiting valve at PSLF and PSVF
(pressure specification in bar)
Non piloted: PSL(V)F ...- 3
Piloted: PSL(V)F ...- 5
Table 9: Tool adjustable pressure limiting valve for the main
pressure.
Adjustable from 50 up to 400 bar, after loosening the
lock-nut (for symbol, see sect. 3.1.1 and 3.1.2).
These additional elements are illustrated in flow pattern symbols of size 3,
they do apply to size 5 in the same way.
PSLF A 1(2)./...-3(5)
PSVF A 1(2)./...-3(5)
PSL(V)F A..D, V
PSL(V)F..PA (PB,PD)
PSL(V)F A..X
PSL(V)F A..F, Z, ZM
PSL(V)F A..D..
PSL(V)F A..F..
Table 7: Coding for control oil supply (for symbol, see sect. 3.1.1
and 3.1.2)
no coding Without pressure reducing valve for actuation cod-
ing A, C or P acc. to sect. 3.2, table 18 or in the
case of external control oil supply (20-40 bar) for
other actuations
1
2
With integrated pressure reducing valve for internal
control oil supply for actuations coding H (HA, HEA,
F, FA, FEA).. and E(EA).. or as pick-up for other
control valves (max. permissible control oil flow
approx. 2 lpm)
Control pressure:
Coding 1: approx. 20 bar (+ return pressure at R)
Coding 2: approx. 40 bar (+ return pressure at R)
Coding
Table 8: Arbitrary idle pump circulation of all consumers by
means of 2/2-way solenoid valve type WN 1 acc. to
D 7470 A/1.
2/2-way solenoid valve type EM 21 DE (DSE) acc. to
D 7490/1 E for prop. pressure limitation only.
Note: To limit the control oil flow, when using the idle pump
circulation with type PSV an additional element coding S,
W or B 4, B 5, B 6 acc. to table 5 is required.
Attention: Observe note in sect. 6.1 a !
Description
Coding Description
Coding Description
no coding If not required
F
With WN 1 F, idle pump circulation if valve is de-
energized (emergency stop)
D
With WN 1 D, idle pump circulation if valve is
energized
F...
or
D...
With pressure limiting valve, which can be activat-
ed as a second pressure stage (specify pressure in
bar) (pre-set pressure, tool adjustable from 50 to
400 bar). Example:
PSLF A 1 F100/350-3..
De-energized p
max
= 100 bar
Energized p
max
= 350 bar
PA, PB,
PD
Prop. pressure limiting valve enabling variable
adjustment of the system pressure; Pressure range:
PA 100...320 bar, PB 15...250 bar, PD 18...400 bar
Z
Prop. pressure limiting valve type EM 21 DSE,
open when deenergized
ZM
Like Z, but with lead sealed wing screw for emer-
gency operation
V
Prop. pressure limiting valve type EM 21 DE, closed
when deenergized
X...
Additional LS pressure limitation (50...400 bar)
Not suited to compensate pressure peaks on the
consumer side.
Table 8
D 7700-F page 7
Table 10: Solenoid voltage and version
G 24 EX
G 24 EX-10 m
For use in areas with explosion hazardous atmosphere. Suited for category 2 and 3, zone 1, 21, 2, 22.
Protection class EEx m II 120° (T4),
with cable length 3 m (no coding) or 10 m
EX
TEX
EX4
TEX4
3-pin actuation solenoid
3-pin actuation solenoid with manual emergency actuation
4-pin actuation solenoid
4-pin actuation solenoid with manual emergency actuation
Like G 24 EX .. , but for ambient temperature < 70°C
G 12 IS
G 12 IS-10 m
G 24 TEX 70
G 24 TEX 70-10 m
For use in mines and its on-surface systems, which can be endangered by fire damp and/or combustible dust.
Protection class I M2 Ex d ib I (fire-damp protected), with cable length 5 m (no coding) or 10 m
G 24 MSHA
G 24 MSHA-10 m
For use in mines and its on-surface systems, where a ATEX (EU), IEC, MSHA (USA) or MA (China) approval is
mandatory.
Protection class I M2 Ex d I (fire-damp protected), with cable length 5 m (no coding) or 10 m
G 24 M2FP
G 24 M2FP-10 m
For use in mines and its on-surface systems, where a IEC or ANZE (Australia) approval is mandatory.
Protection class I M2 Ex d I (fire-damp protected), with cable length 5 m (no coding) or 10 m
Description
Coding
G 12 .
G 24T
Electr. connection conf. EN 175 301-803 A, via plug (MSD 3-309)
Suffix: Applies only to the solenoid actuation coding E, EA, HEA, FEA (table 20) and the functional cut-off
(coding F, FP, table 17), see also sect. 4.3
X 12 .
X 24 .
Electr. connection conf. EN 175 301-803 A, without plug. For options, see coding G...
S 12 .
S 24 T
Electr. connection via quarter turn type plug (Bayonet PA 6 ®, Co. SCHLEMMER D-85586 Poing, suited for
taper with bayonet 10 SL), 3-pin actuation solenoid
AMP 12 K 4
AMP 24 K 4
Vertical connection via plug AMP Junior Timer, solenoid features 4 terminals
DT 12
DT 24
Connection via plug Co. DEUTSCH DT 04-4P, suited for socket DT 06-4S
AMP 24 H 4 T Lateral connection via plug AMP Junior Timer, solenoid features 4 terminals and manual emergency actuation
without
T
TH
H 4
Actuation solenoid 3-pin (standard)
Manual emergancy actuation (standard with functional cut-off F., FP., acc. to table 17)
Manual emergancy actuation with pushbutton (standard with functional cut-off FPH.., FP., acc. to table 17)
4-pin actuation solenoid (only 24V DC)
G 24 C 4
Electr. connection conf. EN 175 301-803 C, via plug (MSD 6-209), 4-pin actuation solenoid
without
T
Suffix:
Manual emergency actuation (standard with functional cut-off FP., table 17)
Note: o Solenoids of explosion-proof design are only available for actuation E, EA or HE (A) (table 20).
o Coding G 24 C4 (X 24 C4) is only available for solenoids of the electrical actuation (table 20) emergency actuation.
o Coding AMP..., DT not available for idle circulation valves coding D, F, PA, PB, PD (table 8), end plates E 3, E 6
(table 11), intermediate plates /ZDS, /ZDR (table 19a), functional cut-off coding F. (table 17)
o Coding S.: Not available for functional cut-off coding F. (table 17) and comparator coding U (table 21)
D 7700-F page 8
3.1.4 End plates of valve bank
Order example:
PSLF A1 F100/380/6 - 5 -... -
E1 - G 24
End plate Description
Table 11: End plates
External
port T
(separate
return pipe
to the tank)
Internal
control oil
return gal-
lery
Order coding of an end plate as
separate part
(example): SLF 5 - E 1
SLF 3 - E 6 - G 24
(State the size: SLF3- or -SLF5- !)
Note: o The internal control oil return gallery is to be
used only in systems where the return pressure is
below 10 bar.
o End plates E.SAE in combination with sub-plates
/..SAE (only size 5) or adapter plate ZPL 5 SAE 3 as
conversion from sub-plates /.SAE size 5 to size 3
Symbols
E1 E2
E1 SAE E2 SAE
E3
E4 E5
E4 SAE E5 SAE
E 1
E 1 SAE
E 4
E 4 SAE
E 2
E 2 SAE
E 5
E 5 SAE
With additional inlet port Y e.g. for
connecting the LS-control pipe of
a subsequent PSVF spool valve
bank.
E 3 E 6 Possibility for arbitrary shut-off of
the idle pump circulation by means
of a directly mounted 3/2-way
direct. seated valve WN 1 H acc. to
D 7470 A/1 (only size 3)
E 7 E 9 Like E 1/E 4, but with additional
return port R (only size 3)
E 8 E10 Like E 2/E 5, but with additional
return port R (only size 3)
Adapter plate to continue a prop.
directional valve bank size 5 with
sections of size 3.
As separate part: SLF 5-ZPL 53
ZPL 53
ZPL 5 SAE 3
Standard end plate
E6
D 7700-F page 9
3.2 Valve sections
3.2.1 Directional spool valve (individual valve)
Order examples:
(valve bank) PSLF A1 F/320/4 - 3 - A2 L 63/40 F1 /EA /3 AN320 BN320 - E1 - G 24
(individual section) SLF 5 - A5 J 160/160 C250 /EA - G 24
Size
Table 13: Spool valve, basic version
Sect. 3.2.2
Note: Size specification is absolutely necessary!
The valve spools are subsequently interchangeable,
e.g. if a different flow rating than initially planned
becomes necessary (see sect. 6.3.4)
Table 19
Table 17
Table 16
Table 15
Table 14
Coding Description
A 2
Standard, with inflow controller, for simultaneous load compensated moving of several consumers
(3/3-, 4/3-way spool valve, standard type)
A 1
Without inflow controller intended for singly / successively actuated functions. Additional functions on the consumer side
are not possible. For the max. consumer flow of the individual section, acc. to table 15 and sect. 6.1 b)
A 5
With inflow controller (for symbol, see coding A 2) but with reinforced spring at the 2-way flow controller (control pres-
sure approx. 9 bar). Only usable in conjunction with connection block type PSLF AH../...-3- or type PSVF with variable
displacement pump / constant pressure system. (See note sect. 6.1 a and b)
A 7
With inflow controller (like coding A 2) but enforced 2-way controller spring (control pressure approx. 13 bar). Only
avail-able in combination with connection block type PSVF and variable displacement pump/constant pressure
system. (See note in sect. 6.1 b)
A 26
A 56
Only size 3: With inflow controller coding A 2 or A 5, and additional rebound damping;
Especially suited for oscillation inducing consumers (e.g. hydraulic motors with a low
number of pistons)
A 8 4/3-way directional spool valve, Makes only sense with flow pattern symbol L and H and maximum flow. Only usable in
conjunction with connection block type PSLF.H./... or type PSVF with variable displacement pump / constant pressure
system. (see note sect. 6.1 b)
AR 2,
AR 5,
AR 7
Like coding A 2, A 5, A 7, but with additional check valve functionality (spool valve = slight leakage),
(see note sect. 6.1 b)
Only usable in conjunction with connection block type PSLF.H./... or type PSVF with variable
displacement pump / constant pressure system.
AX Blanking plate
AA 9 With inflow controller (for symbol, see coding A 2), but with enforced spring for the 2-way flow controller (increased
circulation pressure approx. 18 bar).
Only suited for connection block type PSVF in combination with varaible pump / constant pressure systems.
Attention: Observe note in sect. 6.1 b!
Only available for size 5, cannot be retrofitted!
Available as individual valve coding SLF 5-AA9 or in combination with sub-plate coding /5 SAE, 5 SAE S, /6 D SAE 9,
/6 D SAE 9 S
Table 14: Symbols
L M F H J B R O G
Valve spool with return throttling to assist
oscillation dampening, see sect. 6.1 c
J, B, R, O,
I, Y, Z, V
3/3-way spool valve, observe note in sect. 6.1 cG
4/2-way spool valve, observe note in sect. 6.1 cW
Valve spool with positive overlapping, see sect.
6.1 c, only size 3
A, K, P, Q, T
Valve spool with wider fitting to prevent spool
sticking - intended for contamination prone
systems
2/2-way directional spool valve for hydraulic
motors, see sect. 6.1 e, only size 3
HW, OW
X
D 7700-F page 10
Table 16: LS-pressure limiting valves, only available with spool
valves featuring an inflow controller, coding A 2, A 5
and A 7 (acc. to table 13!). These are no shock valves!
Table 17: Functional cut-off or prop. pressure limitation (only
available with spool valves with inflow controller coding
A 2, A 5 and A 7 acc. to table 13!)
Description
Without functional cut-off
Electric functional cut-off at A or B
Electric functional cut-off at A and B
Prop. pressure limitation for A and/or B
Version FPH. with additional emergency
actuation (no tools needed)
Only size 5: flange sided load signal
ports U and W (G 1/8 (BSPP)) for external
piping, e.g. in combination with sub-plate
/5 S, see sect. 3.2.2 table 21;
Example: SLF 5-A 2 H 160/80 S/5 S
The signal ports are apparent as standard
(see flow pattern symbols on page 11) in
combination with coding A.., B.., A..B..
(acc. to table 15 and 17) and F.1(2, 3), S1
(table 16 and 17)
Load signal ports U and W (G 1/8 (BSPP))
for external piping; tapped ports at valve
section
Coding
no coding
F 1, F 2
F 3
FP 1, FP 2, FP 3
FPH 1, FPH 2, FPH 3
o There remains a residual pressure when the LS gallery is
relieved. When the return line is depressurized the residual
pressure will be: p
relieved
= |p
block
+ |p
controller
(|p
controller
=
control pressure of the inflow controller acc. to table 13)
Coding F., FP. : |p
block
= 10 bar
Coding S, S 1, (X) : |p
block
= 5 bar
o One joint LS-port X is standard on the flange side (see dimen-
sional drawings, sect. 5)
o Size 5: combinations of coding F..1, FP.. or S 1 and solenoids
G 24 MSHA or G 12 IS are not available!
o Coding F.., FP.. not available with solenoids G 24 EX 70 and
G 12 IS
Table 18: Combination possibilities for additional functions
Pressure
limitation
no coding
A or B
A and B
C
The signal ports are apparent as standard (see flow pattern
symbols on page 11) in combination with coding A.., B.., A..B..
(acc. to table 16) and F.1 (2,3), S1 (table 17)
no coding
o
o
o
S 1
o
o
--
F 1, F 2, F 3, S 1
FP 1, FP 2, FP 3
FPH 1, FPH 2, FPH 3
o
o
--
Functional cut-off
S 1
S
Table 15: Max. flow P d A(B) acc. to the coding
Valve spool coding
acc. to table 12
Note: The flow rate for the consumer ports A and B can be individually selected,
e.g. 63/40, 40/80. This provides optimal adaptation to the respective
consumer while exploiting the full functional spool lift. In addition there is
the possibility of mechanical stroke limitation.
Flow coding Q
A, B
(lpm)
at consumer port A and B
Coding
Size
3
5
3
5
3
3
--
4
--
6
6
--
9
--
10
10
--
14
--
16
16
16
22
20
25
25
25
34
32
40
40
40
54
51
63
63
63
85
80
80
80
80
107
110
120
--
120
--
150
160
--
160
--
210
4
--
9
--
14
--
22
20
34
32
54
51
85
80
107
110
--
150
--
210
A 2
A 1,
A 8
A 5
3
5
5
--
10
--
14
--
24
23
37
37
59
60
93
95
118
130
--
175
--
240
A 7
3
5
-- -- -- (30) (47) (75) (118) 150 225 300
AA 9
5
Valid for PSLF (integrated 3-way flow controller: |p ~ 10 bar),
otherwise as guide line Q
A, B
, Q
nom
· 0.2 ·|p
controller
Q
rating
- flow for coding A 2;
|p
controller
stand-by pressure of the flow controller of the pump
Example (size 3): Q
rating
= 25 lpm, |p
controller
= 14 bar;
Q
A, B
, 42 lpm
Coding
no coding
A...
B...
A...B...
C...
Description
Without pressure limitation
Pressure limitation at A with pressure specification
Pressure limitation at B with pressure specification
Pressure limitation at A and B with pressure
specification
Common pressure limitation for A and B with
pressure specification
Pressure limitation p
min
= 50 bar; p
max
= 420 bar
Example: SLF 3-A 2 H63/40 A250 B200/A
D 7700-F page 11
Basic version
(individual section
acc. to table 13)
With respect to flow con-
figuration and actuation,
these symbols are neutral
and must be supplement-
ed by the corresponding
flow pattern symbols
illustrated in table 14, see
also example in sect. 6.2
4/3-way directional
spool valve without
inflow controller
A 1... (A 8...)
4/3-way direction-
al spool valve with
inflow controller
A 2... (A 5...)
Additional function:
Secondary pressure
limitation acc. to table
16 for spool valves with
inflow controller (no
shock valve!)
..A... ..B... ..A...B... ..C...
Functional cut-off,
acc. to table 17, for
spool valves with
inflow controller
Combination possibilities: ..S
(only size 5)
..F(FP, FPH)1
A..F(FP, FPH)1
B..F(FP, FPH)1
A..B..F(FP, FPH)1
..F(FP, FPH)2
A..F(FP, FPH)2
B..F(FP, FPH)2
A..B..F(FP, FPH)2
..F(FP, FPH)3
A..F(FP, FPH)3
B..F(FP, FPH)3
A..B..F(FP, FPH)3
here type F 3here type FP 2here type F 1
Example:
SLF 5-A 2 J63/40
A 250 B 310
F 3/EA-G 24
1
)
1
)
1
)
1
)
1
)
1
)
1
)
1
) Ports U and W on the flange side only with size 5, see description in table 17, coding S
D 7700-F page 12
Table 19: Types of actuation (for further explanations, see sect. 4.3)
Nomenclature Manual actuation Electro-hydraulic
actuation
Hydraulic actuation Pneumatic
actuation
Manipulated
variables
Note: o Approximate values for start of flow at A or B (= min) up to max. consumer flow according to the flow coding table 15,
see curves sect. 4.2.
o Difference between actuation H.. and F.. is the position of the control line ports.
With actuations HE(A) or FE(A) observe also notes and circuit examples in sect. 6.1 i
o
Type E0A, E0C, E0AR prepared for retrofitting of a solenoid actuation
o Type AR, ER, and EAR with detent in end position, stroke limitation not possible
o Type EI - Version without stroke limitation
o Type EM and EAM: Version with pressure gauge ports at the actuation heads
o Type A 8: Actuation torque like with EA. Type E 9, E 9 A: Actuation torque like with H, HA
Actuation angle
min. approx. 5°
max. approx. 30°
Control current ratio
I/I
N
min. approx. 0.2
max. approx. 1
Control pressure
min. approx. 5 bar
max. approx. 18 bar
max. perm. 50 bar
Control press.
min. approx.
2.5 bar
max. approx. 7 bar
Spring
return
Coding
Symbol
BG 3
BG 5
A
E0A
C
E0C
AR
E0AR
E
EI
ER
EA
EAR
F
F UNF
H
H UNF
FA
FA UNF
HA, FA
HA UNF
Detent electro-
hydraulic
Combination
with manual
actuation
hydraulic Combination
with manual
actuation
Combination
with solenoid
and manual
actuation
FEA
FEA UNF
HEA, FEA
HEA UNF
P
PA
Table 20: Additional features for actuations
Type of actuation
/ coding
Suffix Description Example Symbols
A, EA, HA, PA, C 1
Manual actuation without hand lever. For dimensions, see sect. 5.1.3
and 5.2.3
EA 1, C 1
A, EA, HA, PA, C 2 Manual actuation with short hand lever. For dimensions, see sect. 5.1.3
and 5.2.3
EA 2, A 2
A, EA, HA, C V
VA
VB
VC
VCHO
VCHC
Mechanical micro switch (size 3 only), for monitoring the spool‘s idle
position, (for data of the switch, see page 22)
V - Signal with start of movement, direction A or B (no side indication)
VA - Signal with start of movement, direction A
VB - Signal with start of movement, direction B
VC - Signal with start of movement, direction A and B (separate side indication)
VCHO - Signal with start of movement, direction A and B separate (2xNO-contact)
VCHC - Signal with start of movement, direction A and B separate (2xNC-contact)
EA VA,
A 1 VB,
C VC
A, EA, C N, N1
Proximity switch (size 3 only), for monitoring the spool‘s idle position
(no side indication), for data, see page 23
Type N1- only mechanical setup: Proximity switch is customer furnished
(8x8x33 mm central sensor area).
EA N,
A 1 N 1
A, EA, C, PA,
H, HA, F, FA
WA
WA-EX
WA-M2FP
Integrated position sensor (Hall-sensor) with analogous signal output
(lift monitoring)
Coding WA-EX, version for explosion hazardous areas
Coding WA-M2 FP, version with fire-damp protection (mining)
EA WA,
A 1 WA
A, EA, C, PA,
H, HA, F, FA
U
Integrated spool monitoring for side indication
(comparator, triggered signal: ON / OFF)
EA U
A, C, E, E0A G Only size 3: Reinforced version of the spring cover, suitable if high pressure
surges are expected in the gallery T.
E 1 G,
CG,
A 1 G
VA
VC
VB
1 2
WA
U
D 7700-F page 13
3.2.2 Sub-plates
Order example:
PSLF A1 F/320/4-3-A2 L 63/40 A300 F1/EA
/3 AN320 BN320 - E1 - G 24
PSVF A2/300/5-5-A2 J 160/120/EA /Z AN300 BN280/5 - E4 - G 24
Table 21: Sub-plates
Note: Sub-plate with SAE-flange must not be combined with sub-plates (tapped ports) e.g. /5 S.
/3 X, /UNF 3 X,
/UNF 4 W
/4 X
/5 X, /UNF 5 X
Coding Port size for A and B
/53, /533
/534, /UNF 534
ISO 228/1 (BSPP)
G 1/2
G 3/4
G 1/2
G 3/4
G 1
SAE J 514
--
1 1/16-12 UNF-2B
7/8-14 UNF-2B
(1 1/16-12 UNF-2B)
--
1 5/16-12 UNF-2B
--
--
--
--
3
3
5
Size
5
Joint load signal pick-up port X for external circuitry
Description
/3, /UNF 3 G 1/2 7/8-14 UNF-2B 3 Standard
/38 G 1/2 -- 3 Sub-plate for pre-selector valve type SLF 3-A 8
/4, /UNF 4 G 3/4 1 1/16-12 UNF-2B 3 Standard
/5 G 1 -- 5 Standard
/3 AN... BN...
/3 AN...
/3 BN...
/UNF 3 AN... BN...
/UNF 3 AN...
/UNF 3 BN...
G 1/2 7/8-14 UNF-2B 3 Shock and suction valves at A and B or A or B
(state pressure in bar)
/3 A... B...
/3 A...
/3 B...
G 1/2 -- 3
/5 S G 1 -- 5
Shock valves at A and B or A or B (state pressure in bar)
Load signal pick-up ports U and W (G 1/4 (BSPP)) for external
circuitry
Sub-plate for valve section size 3 in a valve bank size 5
(saving an intermediate plate)
/58 G 1 -- 5 Sub-plate for pre-selector valve type SLF 5-A 8
SAE 1” (6000 psi)
/5 SAE, /5 SAE S,
/5 SAE 8
5 Sub-plate with SAE-flange, analogue /5, /5 S and /58
SAE 1 1/4” (6000 psi)
/6 D SAE (S)
1
)
/6 D SAE 9 (S)
5
5
Sub-plate with SAE-flange for combination of two valve
sections, to achieve a load compensated consumer flow of
max. 400 lpm
/U 3
/U 5
3
5
Sub-plate for mounting ancillary blocks with additional func-
tions, acc. to table 21a (size 3) and table 21 b (size 5)
--
--
/U 53 5
Like /533, but prepared for mounting ancillary blocks with
additional functions, acc. to table 21a (size 3)
/Z AN..BN.. Intermediate plate with shock and suction valves --
1
) Discontinued, do not use for new designs!
D 7700-F page 14
/3, /4, /5, /53, /533, /534
/5 SAE, /UNF 3, /UNF 4,
/UNF 5, /UNF 534
/38, /58
/5 S, /5 SAE S
/3 AN..., /UNF 3 AN
/3 BN.... (analog)
/3 A... B...
/3 A...
/3 B... (analog)
Symbols
/3 AN... BN...
/UNF 3 AN... BN...
/3 X, /4 X, /5 X,
/UNF 3 X, /UNF 5 X
/6 D SAE
/6 D SAE 9
/UNF 4 W /Z AN..BN..
1
)
1
) Gauge ports a and b only with coding /4, /4 X, /5, /UNF 5
Gauge ports MA and MB only with coding /UNF 534 and /UNF 5 X
2
) Port X only with /5 SAE S
1
)
2
)
/U 3, /U 5, /U 53
/6 D SAE S
/6 D SAE SS
D 7700-F page 15
Table 21a: Ancillary blocks size 3
Port size: /3.. = G 1/2 (BSPP), /4.. = G 3/4 (BSPP), /UNF 3.. = 7/8-14 UNF-2B (SAE-10), /UNF 4.. = 1 1/16 UNF/2B (SAE/12)
Order example: PSLF A1 F/320/4-3-A2 L 63/40 A300 F1/EA/
U3/3 AL-6-A 7/200 - E1 - G 24
Coding Brief description Symbols
/3
/UNF 3
/4
Without additional
functions
/3 AS... BS...
/31 AS... BS...
/UNF 3 AS... BS...
/4 AS... BS...
With shock valves
at A and B (routed
to the opposing
side), with pressure
specification (bar)
/3 AN... BN...
/31 AN... BN...
/UNF 3 AN... BN...
/4 AN... BN...
With shock and
suction valves at A
and B, with pres-
sure specification
(bar)
/4 AN BN
/UNF 3 AN BN
With shock and suc-
tion valves at A or B
/4 AN...
/4 BN...
With shock and
suction valves at A
or B, with pressure
specification (bar)
/3 AL...
/3 BL...
/3 AL... BL...
/3 AC... BC...
With over-center
valves at A and/or B.
Type /3 AC... BC...
load independent
version (for data,
see D 7918, type
LHT 3)
(For more details,
see D 7918 type
LHT 3)
Coding Brief description Symbols
/43 DFA
/43 DFB
For regenerative
circuit piston side
connected at A
(type /43 DFA) or
piston side connected
at B (type /43 DFB)
Note:
Not suitable for the
use with dragging
loads!
/3 VV
/UNF 3 VV
/3 VX
/UNF 3 VX
/3 XV
/UNF 3 XV
With shut-off val-
ves EM 32 V acc. to
D 7490/1 (one or both
sides) blocking the
consumer with zero
leakage (Q
max
approx.
80 lpm)
/3 DRH
/UNF 3 DRH
Releasable check
valves in A and B
(release ratio 1: 2.5)
For additional version
with pre-relieve co-
ding /3 DRH VV, see
D 6110 type DRH 3
- 6 - A 7 - 250
Pressure setting (bar)
Flow (lpm) / Release ration
Coding A 7 B 7 C 7 D 7 E 7 F 7
(lpm) 130 85 55 35 20 10
Bypass-throttle D2
Coding
(# mm)
Release
ratio
0
plugged
1:7
4
0.4
1:4.96
5
0.5
1:3.5
6
0.6
(std.)
1:2.28
7
0.7
1:1.28
8
0.8
1:0.93
D 7700-F page 16
/ZDR
/ZDS
Intermediate plate
with short-circuit
valve between A and
B (floating function) for
volumetric interchange
Q
max
= 20 lpm
/ZDRH Releasable check val-
ves in A and B (release
ratio 1:2.5)
For additional version
with pre-relieve coding
/ZDRH VV, see D 6110
type DRH 3
/ZAL... BL...
With over-center val-
ves at A and B. For co-
dings, see /3 AL.. BL..
or pamphlet D 7918
type LHT 3)
Spacer plate 40 mm
to compensate height
differences between
differing ancillary blocks
or to prevent collisions
of neighboring ancillary
blocks when combined
with other intermediate
plates
/Z 40
/Z 40 M
/Z 40 M UNF
/Z AN BN With suction valves at
A and B
/Z 40 M
/Z 40 M UNF
Intermediate plates for parallel connection
to table 21 a
D 7700-F page 17
Symbols
/Z 30
/5 DRH
/UNF 5 DRH
/5 VV
/UNF 5 VV
/5 VX
/UNF 5 VX
/5 XV
/UNF 5 XV
Coding
Spacer plate 30 mm
to compensate
height differences
between differing
ancillary blocks or
to prevent collisi-
ons of neighboring
ancillary blocks
when combined
with other interme-
diate plates
Additionally all intermediate plates for parallel connection acc. to D 7700-5
can be used.
Releasable check
valves in A and B
(releaseratio1:2.5)
For additional
version with pre-
relieve coding
/5 DRH VV, see
D 6110 type
DRH 5
With shut-off val-
ves EM 42 V acc.
to D 7490/1 (one
or both sides)
blocking the con-
sumer with zero
leakage (Q
max
approx. 160 lpm)
/54 DFA
/54 DFB
For regenerative
circuit piston side
connected at A
(type /54 DFA) or
piston side con-
nected at B (type
/54 DFB)
Note:
Not suitable for the
use with dragging
loads!
/54 DEA
/54 DEB
With switch able
regenerative cir-
cuit functionality
via 2/2-way valve
type EM 41 S
Brief description
Table 21b: Ancillary blocks size 5
Port size: /5.. = G 1, /.4.. = G 3/4, /UNF 5.. = 1 5/16-12 UNF-2B (SAE-16)
Order example: PSVF A2/300/5-5-A2 J 160/120/EA/U 5/5 VV- E4 - G 24
/4 ASN.. BSN..
/5 AN..
/5 BN..
/5 AN.. BN..
/UNF 5 AN... BN...
/5 AS... BS...
/UNF 5 AS... BS...
Coding
/5
/UNF 5
Symbols
With shock valves at A
and B, with pressure
specification (bar)
With shock and suc-
tion valves at A and B,
with pressure specifi-
cation (bar)
With shock and suc-
tion valves at A or B,
with pressure specifi-
cation (bar)
/5 R VV
With by-pass valves
type EM 22 V acc. to
D 7490/1 for arbitrary
customer relieve.
Note: Q
max
= 40 lpm
With shock valves at
A and B (routed to the
opposing side), with
pressure specifica-
tion (bar)
Brief description
Without additional
functions
- 6 - A 6 - 250 -
Pressure setting (bar)
Flow (lpm) / Release ration
Bypass-throttle D2
Coding A 6 B 6 C 6 D 6 E 6 F 6
(lpm) 250 200 150 100 50 25
0 4 5 6 7 8
plugged 0.4 0.5 0.6 0.7 0.8
(std.)
1:6 1:4.26 1:3 1:1.95 1:1.56 1:0.79
Coding
(# mm)
Release
ratio
/5 AL..
/5 BL..
With over-center val-
ves at A and/or B.
(For more details, see
D 7918 type LHT 5)
Intermediate plates for parallel connection
/Z ALW-..
/Z BLW-..
With over-center
valve for A or B and
add. shuttle valve.
For type coding,
see coding /5 AL or
/5 BL
D 7700-F page 18
4. Characteristic data
4.1 General and hydraulic
Type coding
Design
PSLF, PSVF and SLF
Directional spool valve for manifold mounting, up to 12 spool valves (size 3) or 10 spool valves
(size 5) may be combined in a valve bank by means of sub-plates, all-steel design
Any
P = Pressure inlet (pump)
R = Return
A , B = Consumer ports
U, W, X = Load-signal outlet at the indiv. spool valve section
LS = Load-signal outlet e.g. connection of pump metering valve at PSVF.
Attention: No pressure input!
M = Pressure gauge connection (pump side)
Z = Pilot pressure connection (20...40 bar inlet, 20 or 40 bar outlet)
T = Control oil return port
Y = Load-signal inlet port (end plate E 2 and E 5)
Installation position
Ports
Size 3 5
Inlet section PSLF, PSVF../.., PSVF..- 3.8
1
) 3.3
1
)
Valve section Actuation A, E, F, H, P 4.4
2
) 6.6
2
)
EA, PA 4.8
2
) 7.0
2
)
FA, HA 4.7
2
) 6.6
2
)
FEA, HEA 5.1
2
) 7.1
2
)
Blanking plate AX 0.9 --
Intermediate plate /Z AN..BN.. -- 3.1
Sub-plates /3, /38, /4, /5, /53, /533, /534,
/5 S, /3 X, /5 X, /6 2.2 4.3
/3 AN... BN..., /3 A..B.. 2.5 --
/5 SAE, /5 SAE S, /5 SAE 8 -- 9.2
/6 D SAE -- 17.0
End plates E 1, E 2, E 4, E 5 0.8 1.8
E 3 and E 6 2.1 3.1
E 7, E 8, E 9, E 10 2.0 --
E 1 SAE ... E 5 SAE -- 2.9
Adapter plate ZPL 53, ZPL 5 SAE 3 5.0
Size 3 Size 5
Indiv. section 4 x M8 4 x M10
Valve bank M8 M10
Mounting
See dimensional drawings
in sect. 5 ++
1
) + 0.6 kg
at version with
solenoid valve
WN 1 F(D), PA...PD
acc. to table 8
2
) + 0.4 kg
at version with
functional cut-off
(coding F.., FP.., FPH..
acc. to table 16)
P, R, A, B = Acc. to dimensional drawings (see sect. 5.1)
M, LS, Z, T, Y = G 1/4 conform. ISO 228/1 (BSPP)
U, W, X = Acc. to dimensional drawings (see sect. 5.1 and 5.2)
Indiv. valve section and sub-plates: All surfaces corrosion-inhibiting, gas nitrided
(Solenoid at actuation E... and additional functions F1...F 3, FP 1...FP 3, FPH 1...FPH 3 inc
galvanized and olive-green anodized)
Port size
Surface coating
Mass (weight) approx. (kg)
Temperature Ambient: approx. -40 ... +80°C; Fluid: -25 ... +80°C, pay attention to the viscosity range!
Start temperature down to -40°C are allowable (Pay attention to the viscosity range during start!),
as long as the operation temperature during consequent running is at least 20K (Kelvin) higher.
Biodegradable pressure fluids: Pay attention to manufacturer‘s information. With regard to the
compatibility with sealing materials do not exceed +70°C.
Observe restrictions for versions with ex-proof solenoid!
Rec. contamination class
Operating pressure
ISO 4406 20/18/15
p
max
= 400 bar; Ports P, P1, A, B, LS, M, Y
The max. pressure achievable at the consumer side of the spool valves is lowered by the amount
equivalent to the internal control pressure drop at the 3-way flow regulator of the PSLF (see curves)
or at the pump flow regulator (PSVF)..
Return port R(R1) 50 bar; port T pressure less with separate pipe (e.g. 8x1) to the tank. It is
recommended to employ end plate E 1, E 2, E 3, etc. with an additional leakage port, in case
higher return pressure is anticipated. Port Z approx. 20 or 40 bar (acc. to coding, acc. to table 7)
(outlet); 40 bar (inlet)
Control circuit
Flow
For control pressure, see Q-I-characteristics. The internal control oil circuit is sufficiently
protected against malfunctions caused by contamination by means of a disk filter.
Acc. to the specifications in table 14, in sect. 3.2.1
Pressure fluid Hydraulic fluid (DIN 51524 table 1 to 3); ISO VG 10 to 68 (DIN 51519)
Viscosity range: min. 4; max. 1500 mm
2
/sec; Optimal operation range: 10...500 mm
2
/sec
Also suitable are biodegradable pressure fluids of the type HEPG (Polyalkylenglycol) and HEES
(synth. Ester) at operation temperatures up to +70°C. HETG (e.g. rape seed oil) or water based
fluids e.g. HFA or HFC must not be used!
D 7700-F page 19
4.2 Curves
Main pressure limiting valve in the inlet section
Inlet section PSLF A..
Circulation pressure PdR
Prop. pressure limitation
Coding PA ... PD acc. to table 8, sect. 3.1.3
Coding FP(H) 1, FP(H) 2, FP(H) 3
acc. to table 16, sect. 3.2.1
2-way inflow controller
Directional spool valve section PdA(B), A(B)dR
Size 3
Size 5
Oil viscosity during
measurement approx.
60 mm
2
/sec
Consumer flow curves (guide line, example is valve section with inflow controller type SLF. - A2 ../..)
Flow coding
acc. to table 14
Flow coding
acc. to table 14
Flow coding
acc. to table 14
PSL(V)F A../..-3 PSL(V)F A../..-5
Pressure setting (bar)
Back pressure |p (bar)
Load pressure (bar)
Pressure setting (bar)
Back pressure |p (bar)
Flow Q (lpm)
Flow Q (lpm)
Flow Q (lpm) Flow Q (lpm)
Flow Q (lpm) Flow Q (lpm)
Control current I (A)
Consumer flow Q
A, B
(lpm)
Control current I (A)
c 24V DC
Control current I (A)
c 12V DC
c Control pressure (bar)
hydr. actuation H, F
c Angle at hand lever (°)
manual actuation A, C
A(B) dR (spool
valve L,M,F,H)
A(B) dR (spool
valve L,M,F,H)
D 7700-F page 20
Actuating moment (Nm) size 3 / 5
Idle position End position
Version A approx. 2.3 / 3.0 approx. 3.4 / 7.5
Version FA, FEA, HA, HEA, PA approx. 2.9 / 5.0 approx. 8.0 / 16.5
Version EA, E0A approx. 2.4 / 3.0 approx. 6.0 / 12.0
4.3 Actuations
For other data, such as codings, symbols etc., acc. to table 19 sect. 3.2
Actuation A
Version with detent, fixation of the valve spools at any desired position (idle position with special notch)
Version with detent, fixation of the valve spool at idle and both end positions
Required pulse duration for switching: approx. 1 sec
Actuation C
AR, ER, EAR
Prop.-Solenoid, manufactured and tested acc. to DIN VDE 0580
Twin solenoids are of wet armature design. The hydraulic fluid provides lubrication and protection
against corrosion.
Actuation E, EA, HE, HEA,
FE, FEA
Specifications apply to all solenoid versions if not stated otherwise.
Nom. voltage U
N
24V DC 12V DC
Coil resistance R
20
26.6 { 6.3 {
Current, cold I
20
0.9 A 1.9 A
Lim. current I
G
(I
lim
) 0.63 A 1.26 A
Cut-off energy W
A
0.3 Ws 0.3 Ws
Rel. duty cycle S 1 S 1
(reference temp. }
11
= 50°C)
Required dither frequency 40...70 Hz
(best 55 Hz)
Dither amplitude A
D
1
) 20% A
D
50%
Additional notes:
See also Sk 7814, as well as
for additional components
sect. 6.1 j !
Control current I/I
G
Oil viscosity during mea-
surement approx. 60 mm
2
/s
I - stroke- curve
1
) A
D
(%) = · 100
I
peak - peak
I
G
Electrical connection Circuitry
for coding -G 12, -G 24
-X 12, -X 24
EN 175 301-803 A
3-pin
IP 65 (IEC 60529)
Circuitry
for coding -AMP 12 K 4
-AMP 24 K 4
AMP Junior Timer,
4-pin
IP 67 (IEC 60529)
The IP-specification only applies when the plug is mounted as specified.
Circuitry
for coding -S 12
-S 24
3-pin
IP 67 (IEC 60529)
Circuitry
for coding -G 24 H 4
4-pin
IP 65 (IEC 60529)
Circuitry
for coding -G 24 C 4
EN 175 301-803 C
4-pin
IP 65 (IEC 60529)
3-pin
Coil a (1) Coil b (2)
4-pin
Coil a (1) Coil b (2)
3 1 2 4 (with coding
...H 4 and ...C 4)
Circuitry
for coding -DT 12
-DT 24
4-pin
IP 69 K (IEC 60529)
D 7700-F page 21
Letter of conformity ATEX TÜV-A 02ATEX 0007 X
Ex-proof level O II 2 G Ex mb II 120°C (T4)
O II 2 D Ex mbD 21 T120°C
Duty cycle S 1, one coil energized per solenoid housing
Protection class IP 67 (IEC 60529)
Nom. voltage U
N
24V DC
Coil resistance R
20
26.6 {
Current, cold I
20
0.88 A
Lim. current I
G
0.63 A
Max. residual ripple of the 15% supply voltage
Conditions of use:
Ambient temperature -35 ... +40°C
Max. fluid temperature +70°C
Fuse I
F
< 1.8 A each solenoid must be safe guarded
against overload and short-cut by fuse conforming
IEC 60127 medium
Surface coating Housing zinc galvanized
Coil and connection cavity are molded
Electrical design and testing conforming EN 60079-0, VDE 0170/0171 T1 and T9
Electrical connection 4 x 0.5 mm
2
Cable length 3 m or 10 m (cable ÖLFLEX-440P ® Co. LAPP,
D-70565 Stuttgart)
For connection scheme. see “Actuation E, EA” (standard version)
Explosion-proof version of actuation E, EA, HE(A)
Voltage specification G 24 EX, G 24 TEX
Attention:
Additionally observe operating manuals
B 01/2002 and B ATEX
Protect against direct sun light !
Not available in combination with other sole-
noids at the connection block (table 3a and 8),
ancillary blocks (table 19), intermediate plates (table
22), end plates (table 11) and functional cut-off F..
(table 17).
Letter of conformity IEC IEC Ex IBE 09.0005 X
Letter of conformity ATEX IBExU07 ATEX 1089 X
Ex-proof level O II 2 G Ex d IIB T4
O II 2 D Ex tD A21 T135°C
Duty cycle S 1, one coil energized per solenoid housing
Protection class IP 67 (IEC 60529)
Nom. voltage U
N
24V DC
Coil resistance R
20
80 {
Lim. current I
G
0.24 A
Max. residual ripple of the 15% supply voltage
Conditions of use:
Ambient temperature -20 ... +70°C
Max. fluid temperature +70°C
Fuse I
F
< 0.5 A each solenoid must be safe guarded
against overload and short-cut by fuse conforming
IEC 60127 medium
Surface coating Housing zinc galvanized
Coil and connection cavity are molded
Electrical design and testing conforming, EN 60079-0, VDE 0170/0171 T1 and
T9
Electrical connection 4+1 x 0.5 mm
2
Cable length 3 m or 10 m (cable ÖLFLEX-440P ® Co. LAPP,
D-70565 Stuttgart)
For connection scheme. see “Actuation E, EA” (standard version)
Explosion-proof version of actuation E, EA, HE(A)
Voltage specification G 24 TEX 70
Attention:
Additionally observe operating manuals
B 09/2006 und B ATEX
Protect against direct sun light !
Not in to combination with functional cut-off
F(FP).. (table 17) or all other solenoids mounted on
connection blocks (table 3 a, 8), ancillary blocks
(table 19), intermediate plates (table 22) and end
plates (table 11)
Coil a (1) Coil b (2)
Letter of conformity ATEX TÜV-A 02 ATEX 0007 X
Ex-proof level O II 2 G Ex mb II 120°C (T4)
O II 2 D Ex mbD 21 T120°C
Duty cycle S 1, one coil energized per solenoid housing
Protection class IP 67 (IEC 60529)
Nom. voltage U
N
24V DC
Coil resistance R
20
26.6 {
Current, cold I
20
0.88 A
Lim. current I
G
0.63 A
Max. residual ripple of the 15% supply voltage
Conditions of use:
Ambient temperature -35 ... +40°C
Max. fluid temperature +70°C
Fuse I
F
< 1.8 A each solenoid must be safe guarded
against overload and short-cut by fuse conforming
IEC 60127 medium
Surface coating Housing zinc galvanized
Coil and connection cavity are molded
Electrical design and testing
conforming EN 60079-0, VDE 0170/0171 T1 and T9
Electrical connection 4 x 0.5 mm
2
Cable length 3 m or 10 m (cable ÖLFLEX-440P ® Co. LAPP,
D-70565 Stuttgart)
For connection scheme. see “Actuation E, EA” (standard version)
Explosion-proof version of actuation E, EA, HE(A)
Voltage specification G 24 EX 4, G 24 TEX 4
Attention:
Additionally observe operating manuals
B 01/2002 and B ATEX
Protect against direct sun light !
Not in to combination with functional cut-off
F(FP).. (table 17) or all other solenoids mounted on
connection blocks (table 3 a, 8), ancillary blocks
(table 19), intermediate plates (table 22) and end
plates (table 11)
Coil a (1) Coil b (2)
Coil a (1) Coil b (2)
D 7700-F page 22
The idle position of the valve spool is monitored by a contact switch from
Co. BURGESS type V 4 N 4 Sk 2 ® with lever AR 1
Switch engaged at idle position
Electr. connection via plug, e.g. type G 4 W 1 F ® Co. HIRSCHMANN,
www.hirschmann.com, (not scope of delivery)
Protection class IP 65 (IEC 60529)
Circuit-breaking capacity
up to 30V DC = 5 A
Inductive load = 3 A
Actuation suffix VCHO, VCHC
(only size 3)
The idle position of the valve spool is monitored by a contact switch from
Co. BURGESS type V 4 NS ® with lever AR 1
Switch engaged at idle position
Protection class IP 67 (IEC 60529)
Circuit-breaking capacity
up to 30V DC = 5 A
Inductive load = 3 A
Cables 3 x 0.5 mm
2
leads PVC coated; length; 50 mm
black = inlet
blue = NO-contact
green = NC-contact
The switch is highly protected by a sheet cover against exterior physical damage
Actuation suffix V, VA, VB, VC
(only size 3)
Control pressure approx. 5 bar (start of movement)
approx. 18 bar (max. movement) max. perm. pressure 50 bar
The remote control pipes to the control ports 1 and 2 must be externally piped.
Supply is via proportional pressure reducing valve e.g. type FB2/18 etc. or KFB2/18
(both acc. to D 6600)
Actuation H, HA, HEA, F, FA, FEA
Control pressure approx. 2.5 bar (start of movement);
approx. 7 bar (max. movement)
Actuation P, PA
MSHA-approval (USA) 18-NXA 05 0003-0
MA-approval (China) J2007101
Letter of conformity IEC IEC Ex IBE 09.0004 X
Letter of conformity ATEX IBExU05 ATEX 1115 X
Ex-proof level O I M2 Ex d I
Duty cycle S 1, one coil energized per solenoid housing
Protection class IP 67 (IEC 60529)
Nom. voltage U
N
12V DC 24V DC
Coil resistance R
20
6.3 { 26.6 {
Lim. current I
G
1.33 A 0.63 A
Current. cold I
20
1.9 A 0.9 A
Conditions of use:
Ambient temperature -20 ... +40°C
Max. fluid temperature +70°C
Fuse I = max. 3x I
G,
each solenoid must be safe guarded
against overload and short-cut by fuse conforming
IEC 60127-2 UL 248
Surface coating Housing zinc galvanized
Coil and connection cavity are molded
Electrical design and testing conforming EN 60079-0 (general requests),
EN 60079-1 (pressure resistant encapsulation “d”)
Electrical connection 4 x 18 AWG (approx. 0.8 mm
2
)
Cable length 3 m or 10 m
Leads BK, WH, RD, GN; Item-Nr. 40003, General Cable
For connection scheme. see “Actuation E, EA” (standard version)
Explosion-proof version of actuation E, EA
(fire-damp protected (mining))
Voltage specification G 24 MSHA
Attention:
Additionally observe operating manuals
B 05/2006 and B ATEX
Not available in combination with other
solenoids at the connection block (table 3a
and 8), ancillary blocks (table 19), intermedi-
ate plates (table 22), end plates (table 11) and
functional cut-off F(FP) .. (table 17).
Exception: A combination with functional
cut-off FP.. (table 17) together
with intermediate plate 7709 090
is available.
Coil a (1) Coil b (2)
Letter of conformity ATEX IBEx U05 ATEX 1115 X
Letter of conformity ANZEx ANZEx 10.3019X
Electrical connection 4 x 0.75 mm
2
, shielded connection line
For additional information see coding G 24 MSHA
Explosion-proof version of actuation E, EA, HE(A)
(fire-damp protected (mining))
Voltage specification G 24 M2FP
Coil a (1) Coil b (2)
D 7700-F page 23
VCHOCircuitry VCHC
Switch function
S 1 - direction A
S 2 - direction B
Supervision of the idle position of the valve spool via a transducer
Design 8x8x40 mm, with LED
NC-contact, conducting to plus type IFFM 08P/37O1/02L
Manuf.: Co. BAUMER Electric GmbH D-61169 Friedberg
Input power #3 mm, 3 leads PVC coated, length 2 m
Operating voltage 10 up to 30V DC
Current consumption without load up to 10 mA
Max. load current 200 mA
Operating temperature -25°C up to 80°C
Protection class IP 67 (IEC 60529)
The switch is highly protected by a sheet cover against exterior physical damage.
Actuation suffix N
(only size 3)
Position sensor, supervision of the valve spool stroke via a Hall-sensorActuation suffix WA, WA-EX
Signal voltage
U
B
= Supply voltage
U
B max
= 76%
U
B min
= 24%
Accuracy * 9% (U
B
)
Actuation suffix U Comparator
(lift monitoring / side indication)
Electrical connection acc. to coding, acc. to table 10
Pin Signal Description
1 OUT
A
PNP-transistor
(conducting to plus)
2 OUT
B
PNP-transistor
(conducting to plus)
3 +U
B
10 ... 32V DC
4/GND GND 0V DC
Open-Collector:
I
max
= 10 mA
short-circuit proof
Residual ripple 10%
Coding G...
Circuitry
2 = +U
B
operating
voltage
(5 up to 10V)
1 = U
output
3 = GND
Coding G...
Circuitry
The DC supply voltage must be stabilized and smoothened.
Attention: The will be permanently damaged, when exposed to a strong magnetic field!
Actuation suffix WA
Electrical connection acc. to coding, acc. to table 10
Actuation suffix WA-EX
Letter of conformity ATEX IBEx U09 ATEX 1001X
Ex-proof level O II 2 G Ex d IIB T4
O II 2 D Ex td A21 IP 6x T 135°C
O I M2 Ex d I
Ambient temperature -30 ... +40°C
Electrical connection 3 m or 10 m (cable ÖLFLEX-440 ® with shielding
and YE/GN ground (protectne conductor) Co. LAPP,
D-70565 Stuttgart)
Attention: Operating manual B ATEX and B 10/2008 have to be additionally observed!
Actuation suffix WA-M2FP
Letter of conformity ATEX IBEx U05 ATEX 1115 X
Letter of conformity ANZEx ANZEx 10.3019X
Electrical connection 4 x 0.75 mm
2
, shielded connection line
For additional information see coding G 24 MSHA
Ex-proof level see WA-EX
Ambient temperature -30 ... +40°C
Electrical connection 3 m or 10 m
Coding AMP...
Coding S...
D 7700-F page 24
4.5 Other solenoid valves
Additional
documentation
- Connection blocks
coding Z, ZM, V
Electr. connection
Circuitry
with coding
with PA, PB, PD
wit h c od ing -G 12, -G 24,
-X 12, -X 24
Slim design industrial
standard contact
clearance 11 mm
IP 65 (IEC 60529)
- Connection blocks
coding F, D
- End plates
coding E 3, E 6
- Connection blocks
coding PA, PB, PD
Nom. voltage U
N
Nom. power P
N
Nom. current I
N
weitere Dokumentation
24V DC 12V DC
21 W 21 W
0.63 A 1.2 A
D 7490/1 E (type EM)
24V DC 12V DC
24.4 W 24.4 W
1 A 2 A
D 7470 A/1 (type WN 1, WH 1)
24V DC 12V DC
21 W 21 W
0.63 A 1.26 A
Circuitry
with coding -G 12, -G 24,
-X 12, -X 24
EN 175 301-803 A
IP 65 (IEC 60529)
Circuitry
with coding -S 24
Plug Co. SCHLEMMER
Type SL-10
IP 67 (IEC 60529)
Circuitry
with coding -AMP 12 K 4
-AMP 24 K 4
AMP Junior Timer
2-pin
IP 65 (IEC 60529)
2
1
4.4 Functional cut-off, prop. pressure limitation
On/Off solenoid with manual emergency actuation
Nom. voltage U
N
24V DC 12V DC
Coil resistance R
20
34.8 { 8.7 {
Current, cold I
20
0.69 A 1.38 A
Current, warm I
70
0.48 A 0.97 A
Cut-off energy W
A
0.3 Ws 0.3 Ws
Rel. duty cycle
1
) S 1 S 1
(reference temp. }11 = 50°C)
Electrical connection EN 175 301-803 A
Protection type (assembled) IP 65 (IEC 60529)
Circuitry Coil a Coil b
Prop. solenoid, with manual emergency actuation. For connection pattern, see functional
cut-off. For electrical data, see actuation E, EA.
1
) Note: The duty cycle refers to one coil only of each twin solenoid.
The perm. duty cycle is only 50%, when both coils are energized simultaneously
Functional cut-off
Prop. pressure limitation
Coding AMP...
Signal table
Ident.
No.
1
2
3
Spool
movement
Idle position
middle
P d B
P d A
OUT
A
OUT
B
ON ON
OFF ON
ON OFF
D 7700-F page 25
5. Dimensions
All dimensions are in mm and are subject to change without notice!
M8, 10 deep
5.1 Size 3
5.1.1 Hole pattern of the sub-plate
5.1.2 Inlet section
M6, 8 deep
M8, 10 deep
Inlet section
Valve section
70 (min. distance)
Outline of the inlet
or valve section
Directional seated
valve WN 1 F(D)
acc. to D 7470 A/1
Pressure
limiting valve
(not valid for
type PSVF A..-3)
Valve section
acc. to sect. 5.2
Socket head screw
ISO 4762 M8x65-8.8-A2K
Max. torque 23 Nm
Socket head screw
ISO 4762 M6x75-8.8-A2K
Max. torque 9 Nm
Type PSLF(V) A../..-3 and PSVF A..-3
Ports
A, B
LS, T, U, W, X, Z
L1
#d
10.8
3.2
3.2
O-ring
1
)
PUR 90 Sh
12.37x2.62
4.47x1.78
7.65x1.78
Ports
P
F(R)
M, LS, L1, Z
#d
12
14.5
3.2
O-ring
1
)
PUR 90 Sh
13.94x2.62
15.6x1.78
4.47x1.78
1
) These O-rings are also available as complete seal kits, see also sect. 6.3.5
Inlet section: DS 7700-F 31 Valve section: DS 7700-F 32
Inlet section: Valve section:
e , 12 at PSL
> 15 at PSV
PSLF 3(4)
PSLF 3(4) T
PSLF 3(4) H
PSLF 3(4) HT
d
22
27
40
45
approx. 75
D 7700-F page 26
Type PSLF ..F(D).../...
PSVF ..F(D).../...
Type PSVF ...X...Type PSLF ..F(D)/...
PSVF ..F(D)
PSVF ..F(D)/...
Type PSLF ..Z(V).../...
PSVF ..Z(V).../...
Type PSLF ..PA(PB, PD)/...
PSVF ..PA(PB, PD)
Option ZM
approx. 56
approx. 78
D 7700-F page 27
5.1.3 Individual valve with manual actuation type A, C
1
) Observe this operation area for the hand
lever with customer furnished manifolds!
Socket head screw ISO 4762
M8x90-8.8-A2K, max. torque 23 Nm
1
)
5.1.4 Individual valves with actuation type EA, E0A
Type EA
E0A
Type E
Type EI
Plug may be installed
rotated by 4x90°, with
cable gland
Tapped plugs with actuation
type E0A
(coding 2)
Lever housing at EA and HA
(FA) can be angled at 180°
in the same manner as
described at sect. 6.3.4
2
) This dimension depends on the manufacturer and can be
up to 50 mm depending on the max. permissible size
according to EN 175 301-803 A
at type AR, ER, EAR
approx. 59
approx. 70
approx.
38.5
2
)
D 7700-F page 28
Coding -G 12 IS
-G 24 MSHA
-G 24 M2 FP
Coding -G 24 EX
-G 24 EX 4
Coding -G 24 TEX
-G 24 TEX 4
Coding -G 24 TEX 70
Coding -S 12
-S 24
-S 12 T
-S 24 T
Coding -G(X) 12 T
-G(X) 24 T
Coding -G(X) 24 C 4
Additional solenoid versions
Manual emergency
actuation
Push-button coding TH
Bayonet PA 6
Coding -AMP 12 K 4
-AMP 24 K 4
Coding -DT 12
-DT 24
Coding -AMP 24 H 4 T
1
) Intermediate plate only in combination with actuation type ER and EAR or with coding G
1
)
approx. 37
approx. 34
approx. 24.5
approx. 37
D 7700-F page 29
5.1.5 Individual valves with hydraulic actuation type FA, FEA, F
Type FEA, FEA 1(2)
1
) This dimension depends on the
manufacturer and can be up to 50 mm
depending on the max. permissible
size according to EN 175 301-803 A
Plug may be installed rotated by
4x90°, with cable gland
Ports conf. ISO 228/1 (BSPP) or
(SAE-4, SAE J 514):
1 and 2 = G 1/8 or 7/16-20 UNF-2B
Type F
Type FA
approx. 69
approx. 70
approx. 58
approx. 38.5
1
)
D 7700-F page 30
5.1.6 Individual valves with pneumatic actuation type PA and P
5.1.7 Blanking plate type AX
Mounting screw
4 x socket head screw
ISO 4762-M8x25 - 8.8-A2K, 23 Nm
Ports conf. ISO 228/1 (BSPP):
1 and 2 = G 1/8
approx. 70
D 7700-F page 31
5.1.8 Lift monitoring
Type ... N(1)
Type a
WA 39
U 53
Type ... V (VA, VB, VC)
Type H.WA
Type WA-EX
WA-M2 FP
Type ... WA, U
Type h
... V (VA, VB) 20.5
... VC 27
Port conf. ISO 288/1 (BSPP)
1 = G 1/4
D 7700-F page 32
5.1.9 Valve sections with LS-pressure limitation, functional cut-off and prop. pressure limitation
Type S 1 up to A..B..S 1
Type F 1 up to A..B.. F 3
FP 1 up to A..B.. FP 3
FPH 1 up to A..B.. FPH 3
Type A.. Type B..
Ports conf. ISO 228/1 (BSPP):
W, U = G 1/8
Pushbutton
(manual emergency actuation)
with type FPH..
Type A..B..
Type C..
approx. 57
approx. 53
D 7700-F page 33
5.1.10 Sub-plate
For inlet section
Type /4
/UNF 4
Plugged at
type PSLF
Tapped ports conf. ISO 228/1 (BSPP) or SAE J 514
Coding
/4
/UNF 4
M8, 10 deep
(75 with /UNF 4)
Port
P, R M, LS, Z, T
G 3/4 G 1/4
1 1/16-12 UNF-2B 7/16-20 UNF-2B
For valve sections
Type /UNF 4 W
Coding A, B W, U, X, MW, a, b
/3.. G 1/2 G 1/4
/4.. G 3/4
/UNF 3.. 7/8-14 UNF-2B 7/16-20 UNF-2B
/UNF 4.. 1 1/16-12 UNF-2B
Tapped ports conf. ISO 228/1 (BSPP) or SAE J 514
1
) Port A is omitted with /38
Shock valve
type CMV 2
acc. to D 7710
A-side at
type 3(4)..A(AN)..
Type /3.., / 38, /4..
/UNF 3..
Shock valve
type CMV 2
acc. to D 7710
B-side at
type /3...B(BN)...
Suction
valve
Suction valve
1
)
Coding a b c d e
/3, /UNF 3 38 31 -- 26 --
/4, /UNF 4 42 29 -- 26 --
/38 69 -- -- 42 --
/3 X 38 31 50 26 57
/4 X 42 29 50 26 57
/UNF 3 X 38 31 -- 26 --
/3 A.., /3 B..
/3 A.. B.. 38 31 -- 26 --
/3 AN.., /BN..
/3 AN.. BN..
/UNF 3 AN..
/UNF 3 BN.. 36 32 -- 27 --
/UNF 3 AN.. BN..
D 7700-F page 34
also sect. 5.1.10 Ancillary blocks sub-plates /U 3, /U 53
Type /U 3
Type /3
/UNF 3
/4
/4 AN BN
Type /3 AS.. BS..
/3 AN.. BN..
/4 AS.. BS..
/4 AN.. BN..
/UNF 3 AS.. BS
/UNF 3 AN.. BN..
Type H L a b c e f g k l m
/3 25 84 23 23.5 25 60.5 8 25 12.5 35 13
/UNF 3 30 96 26.25 23.75 21.75 72.25 2 30 17 13.5 34.5
/4 30 105 27.25 25.25 20.75 79.75 2.5 30 16 12 36
/4 AN BN 30 105 27.25 25.25 20.75 79.75 2.5 30 16 12 36
Ports A and B (all types)::
ISO 228/1 (BSPP) SAE J 514 (SAE-10)
/3.., /31.. G 1/2 ---
/UNF 3.. --- 7/8-14 UN-2B
/4.. G 3/4 ---
Ports ISO 228/1 (BSPP) a and b:
/3, /4 G 1/4 ---
/4 AN..,
/4 BN..
Pressure adjustment:
Side B with type ..AS.. BS
Side A with type ..AN.. BN
G 1/8 ---
Socket head screws
ISO 4762-M6xg-A2-70
Max. torque 9.5 Nm
approx. 32
D 7700-F page 35
Type /4 AN..
/4 BN..
Type /31 AS.. BS..
/31 AN.. BN..
Type
/31 AS.. BS..
/31 AN.. BN..
L
70
100
b
16.5
31.5
e
53.5
68.5
f
15
--
Type /3 AL.. BL..
Ports A and B:
/3.. = G 1/2 (ISO 228/1) (BSPP)
/UNF 3.. = 7/8-14 UN-2B (SAE J 514, SAE-10)
Ports a and b:
/3.. = G 1/8 (ISO 228/1) (BSPP)
Socket head screws
ISO 4762-M6x50-A2-70
Max. torque 9.5 Nm
approx. 32
approx. 65
approx. 65
D 7700-F page 36
Type /3 VV(VX, XV)
UNF 3 VV(VX, XV)
Type /3 AL Type /3 BL
Blocking valve
Type EM 32 V omitted with
type /3 XV and /UNF 3 XV
Max. torque 40 Nm
Type H a b c e g
/3 VV(VX, XV) 50 25 20 23 80 50
/UNF 3 VV
/UNF 3 VX 55 27.5 22.5 21 78 55
/UNF 3 XV
Socket head screws
ISO 4762-M6xg-A2-70
Max. torque 9.5 Nm
Blocking valve
Type EM 32 V omitted with
type /3 XV and /UNF 3 XV
approx. 71
approx. 71
approx. 59
approx. 59
D 7700-F page 37
Type /3 DRH
/UNF 3 DRH
Type /43 DFA Type /43 DFB
Ports A and B:
/.3.. = G 1/2 (ISO 228/1) (BSPP)
/.4.. = G 3/4 (ISO 228/1) (BSPP)
/UNF 3.. = 7/8-14 UN-2B (SAE J 514, SAE-10)
/UNF 4.. = 1 1/16-12 UNF-2B (SAE J 514, SAE-12)
Ancillary blocks for sub-plates /U 3
Intermediate plate for parallel connection
Type /ZDR
/ZDS
Type /ZDRH
Type /ZAL..BL.. Type /Z 40
/Z 40 M
/Z 40 M UNF
Type /Z AN BN
Ancillary block
acc. to table 21a
Over-center valve, side A
Over-center valve, side B
Ports a and b:
ISO 228 (BSPP) SAE J 514
/Z 40 M G 1/4 ---
/UNF 3.. --- 7/16 - 20 UNF - 2B
approx. 65
approx. 65
with /Z..M
D 7700-F page 38
End plates of the valve bank
Type E 1, E 2, E 4, E 5
Type E 3, E 6
Type E 7, E 8, E 9, E 10
Port T plugged
with E 6
Ports conf. ISO 228/1 (BSPP):
R = G 3/4
T and Y = G 1/4
Directional seated
valve WN 1 H
acc. to D 7470 A/1
M8, 10 deep
M8, 10 deep
a/f
M8, 10 deep
a/f 17
Torque 46 Nm
Port Y only
apparent with
E 2 and E 5!
Port T plugged
with E 4 and
E 5 !
Port Y
plugged with
E 7, E 9!
Port T
plugged with
E 9, E 10!
approx. 15
D 7700-F page 39
O-ring
1
)
PUR 90 Sh
17.12x2.62
4.47x1.78
7.65x1.78
M10, 11 deep
Ports
P, R
LS, T, U, W, X, Z
L1
#d
15.5
3.2
3.2
M10, 11 deep
1
) These O-rings are also available as complete seal kits, see also sect. 6.3.5
Inlet section: DS 7700-F 51 Valve section: DS 7700-F 52
5.2 Size 5
5.2.1 Hole pattern of the sub-plate
Inlet section Valve section
Valve section:
87 (min. distance)
Outline of the inlet
or valve section
5.2.2 Inlet section
Type PSLF(V) A../..-5 and PSVF A..-5
Pressure limiting valve
(not valid for type
PSVF A..-5)
Ports
#d
O-ring
1
)
PUR 90 Sh
P, F(R)
R, L1, LS, T, Z
16
3.2
17.12x2.62
4.47x1.78
Inlet section:
Valve section
acc. to sect. 5.2
Socket head screw
ISO 4762 M10x60-8.8-A2K
Max. torque 40 Nm
D 7700-F page 40
Type PSL..F(D).../...
PSV..F(D).../...
Type PSV...X...Type PSL..F(D)/...
PSV..F(D)
PSV..F(D)/...
Type PSL..Z(V).../...
PSV..Z(V).../...
Type PSL..PA(PB, PD)/...
PSV..PA(PB, PD)
Option ZM
approx. 56
approx. 78
D 7700-F page 41
5.2.4 Individual valves with actuation type EA, E0A
Type EA
E0A
Type E
Type EI
Tapped plugs with
actuation type E0A.-.
Lever housing at EA and HA (FA) can be
angled at 180° in the same manner as
described at sect. 6.3.4
2
) This dimension depends on the manufacturer and can be up to 50 mm
depending on the max. permissible size according to EN 175 301-803 A.
5.2.3 Individual valve with manual actuation type A, C
1
) Observe this operation area for the hand lever with customer furnished manifolds!
2
) in type AA9...
Socket head screw ISO 4762
M10x90-10.9-A2K-zinc plated
Max. torque 45 Nm
(Coding 2)
1
)
2
)
Plug may be installed
rotated by 4x90°,
with cable gland
at type AR, ER, EAR
approx. 38.5
2
)
approx. 63
approx. 74
D 7700-F page 42
Coding -S 12
-S 24
-S 12 T
-S 24 T
Coding -AMP 12 K 4
-AMP 24 K 4
Coding -G(X) 12 T
-G(X) 24 T
Coding -G(X) 24 C 4
Additional solenoid versions
Coding -AMP 24 H 4 T
Coding -DT 12
-DT 24
Coding -G 24 EX
-G 24 EX 4
Coding -G 12 IS
-G 24 MSHA
-G 24 M2 FP
Coding -G 24 EX 70
Coding -G 24 TEX
-G 24 TEX 4
approx. 34
approx. 37
approx. 37
approx. 24.5
D 7700-F page 43
5.2.6 Individual valves with pneumatic actuation type PA and P
Type HA, FA Type HEA, FEA
Ports conf. ISO 228/1 (BSPP) or
(SAE-4, SAE J 514):
1 and 2 = G 1/4 or 7/16-20 UNF-2B
5.2.5 Individual valves with hydraulic actuation type F or HA, FA, HEA, FEA and H
1
) This dimension (plug) depends on
the make and may be up to 50 mm acc.
EN 175 301-803 A
Plug may be installed rotated by 4x90°,
with cable gland
Type HAType FA
Solenoid with
actuation type
HEA..
Type H
Ports conf. ISO 228/1 (BSPP):
1 and 2 = G 1/8
Type PA
approx. 63 approx. 74
approx. 38.5
1
)
D 7700-F page 44
5.2.8 Valve sections with LS-pressure limitation, functional cut-off and prop. pressure limitation
Type A..B..
Type C..
5.2.7 Lift monitoring
Type WA, U Type WA-EX
WA-M2FP
Type P
Type A..
Type B..
approx. 74
approx. 120
Type a
WA 36.4
U 49.5
D 7700-F page 45
Type S 1 up to A..B..S 1
Type F 1 up to A..B.. F 3
FP 1 up to A..B.. FP 3
FPH 1 up to A..B.. FPH 3
Ports conf. ISO 228/1 (BSPP):
W, U = G 1/8
Pushbutton
(manual emergency actuation)
with type FPH..
5.2.9 Sub-plate
Type /Z AN... BN...
approx. 239
approx. 32
approx. 57
approx. 53
D 7700-F page 46
5.2.11 Sub-plate
For inlet section
Type /6, /UNF 6 Type /7 SAE
M16, 20 deep
M10, 11 deep
Plugged at type
PSLF
M10, 10 deep
a b c
/6 26.5 67 25
/UNF 6 29 68 28.25
Coding
/6
/UNF 6
/7 SAE
Ports
P and R M, LS, Z, T
G 1 1/4 G 1/4
1 5/8-12 UN-2B 7/16-20 UNF-2B
SAE 1 1/2” (6000 psi) G 1/4
Ports conf. ISO 228/1 (BSPP) or SAE J 514
5.2.10 Blanking plate type AX
Mounting screw
4 x socket head screw ISO 4762
M10x35 - 8.8-A2K, 40 Nm
M16, 20 deep
D 7700-F page 47
Type /5 SAE, /5 SAE S, /5 SAE 8
1
)
M12,
15 deep
Type /5, /58, /53, /5 S, /5 X
1
) Type /533, /534, /UNF 534
1
)
Type /UNF 5 X
For valve sections
Type /6 D SAE, /6 SAE 5, /6 D SAE 9, /6 D SAE 9 S
M14,
15 deep
M10,
11 deep
1
) Port A is omitted with /58
Ports conf. ISO 228/1 (BSPP) or SAE J 514
Ports
A, B W, U, X, a, b
G 1 G 1/4
G 1/2 ---
G 1/2 ---
1 5/16-12 UNF-2B 7/16-20 UNF-2B
Coding
/5, /5 S, /58, 5 X
/53
/533
/UNF 5 X
Ports
A, B W, U, X, MA, MB
G 3/4 ---
1 1/16-12 UNF-2B 7/16-20 UNF-2B
SAE 1” (6000 psi) G 1/4
SAE 1 1/4” (6000 psi) ---
Coding
/534
/UNF 534
/5 SAE, /5 SAE S
/6 D SAE (9)
(197.5 when combined with
valve section coding AA 9)
M10, 10 deep
*) at /UNF 534
*)
*)
M10, 10 deep
*)
*)
*)
a b c
/5, /5 S, /5 X 62 32.75 54
/53 55 37.75 44
/58 29.5 32.75 --
a b c
/533 37.75 44 33.5
/534 34.75 50 33.5
/UNF 534 32 57 57
a b c
/6 D SAE (S) 180 28 39
/6 D SAE 9 (S) 197.5 34.6 50.9
D 7700-F page 48
also sect.. 5.2.11 Ancillary blocks for sub-plate /U 5
Socket head screws
ISO 4762-M10x40-A2-70
Max. torque 40 Nm
Port A and B :
/5.. = G 1 (ISO 228/1) (BSPP)
/UNF 5.. = 1 5/16-12 UN-2B (SAE-16, SAE J 514)
Port a and b :
/5.. = G 1/4 (ISO 228/1) (BSPP)
/UNF 5.. = 7/16-20 UNF-2B (SAE-4)
Type /5
/UNF 5
l e f g h k
/5 121.5 31.5 90 47 13 22.5
/UNF 5 119.5 30.5 89 19.5 40.5 23
Type /U 5
/U 53
D 7700-F page 49
Type /5 AS.. BS..
/UNF 5 AS.. BS..
/5 AN.. BN..
/UNF 5 AN.. BN..
Socket head screws
ISO 4762-M10x60-A2-70
Max. torque 40 Nm
Type /5 VV(VX, XV)
Pressure adjustment:
Side A with type /..AS.. BS
Side B with type /..AN.. BN
Pressure adjustment:
Side A with type /..AS.. BS
Side B with type /..AN.. BN
Port A and B :
/5.. = G 1 (ISO 228/1) (BSPP)
/UNF 5.. = 1 5/16-12 UN-2B (SAE-16, SAE J 514)
approx. 32
D 7700-F page 50
Type /5 AN..
/5 BN..
Type /4 ASN.. BSN..
Ports a and b (ISO 228/1) (BSPP):
/5 AL.. = G 1/8
/5 BL.. = G 1/8
Socket head screws
ISO 4762-M10x70-A2-70
Max. torque 40 Nm
Socket head screws
ISO 4762-M10x70-A2-70
Max. torque 40 Nm
Type /5 AL.. Type /5 BL..
Port A and B (BSPP)
/4.. = G 3/4 (ISO 228/1)
/5.. = G 1 (ISO 228/1)
approx. 76
approx. 76
D 7700-F page 51
Type /54 DFBType /54 DFA
Type /54 DEBType /54 DEA
Socket head screws
ISO 4762-M10x70-A2-70
Max. torque 40 Nm
also sect. 5.8 Ancillary blocks
Port A and B acc. to (ISO 228/1) (BSPP):
/4.. = G 3/4
/5.. = G 1
approx. 74
approx. 74
D 7700-F page 52
Type /5 DRH
/UNF 5 DRH
Socket head screws
ISO 4762-M10x70-A2-70
Max. torque 40 Nm
Ports A and B:
/5.. = G 1 (ISO 228/1) (BSPP)
/UNF 5.. = 1 5/16-12 UN-2B (SAE-16)
Type /Z 30
Type /5 R VV
approx. 77approx. 77
Ancillary block acc.
to table 21b
D 7700-F page 53
Type E 1 SAE
E 2 SAE
E 4 SAE
E 5 SAE
M10, 11 deep
a/f 24
Max. torque 180 Nm
End plates of the valve bank
Type E 1, E 2, E 4, E 5
a/f 19
Max. torque 46 Nm
Port T plugged with E 4 and E 5 !
Port Y only apparent
with E 2 and E 5 !
Ports conf. ISO 228/1 (BSPP):
T and Y = G 1/4
Port Y plugged with E 1 SAE
Port T plugged with E 5 SAE
Port T and Y plugged with E 2 SAE and E 4 SAE
approx. 25
D 7700-F page 54
5.2.12 Adapter plate
Type ZPL 53
ZPL 5 SAE 3
ZPL 53
ZPL 5 SAE 3
B
119.5
150
H
62.5
99.5
a
8.25
25
b
85
62.7
c
1
8
18
c2
28
--
d1
55.5
85
d2
--
15
h
13
50
M10, 10 deep
Valve section
size 5
Adapter plate
Type ZPL 5..
Valve section
size 3
D 7700-F page 55
a) Connection block
There are, apart from the standard versions acc. to sect. 3.1.1
and 3.1.2. additional damping variations for the LS-signal
type PSV (coding S or B) duct listed in tables 2 or 4. These are
required, if strong (load-) oscillations are externally induced on
the control circuit. A general rule concerning the use of one or
other variation can however not given.
Coding G
This version lacks the sequence valve at the damping element
which is apparent at the standard version to enable quick
depressurization down to the pre-load pressure during idle
position of the valve spool. This results in a stronger damping
effect than with the standard version, as all fluid from the spring
cavity of the 3-way flow controller must pass the thread type
throttle. Main application is with consumers prone to low frequent
oscillations - drawback is the delayed depressurization down to
the pre-load pressure during idle position of the valve spool
(pro-longed run-down).
Coding H
If on account of the required consumer velocity at least one spool
valve with reference coding A 5 (raised circulation pressure) is
utilized, then, in order to maintain the necessary pressure
difference between 2- and 3-way flow controller, the circulation
pressure of the 3-way flow controller must be raised to approx.
14 bar. This means, of course, greater power dissipation.
Coding Z, ZM, V and PA, PB, PD (acc. to table 8)
When using these valves for an emergency stop function, it has
to be taken into account that there will be a certain min. residual
pressure during pushing load while a valve spool is elevated!
Viscosity $ 60 mm
2
/s
b) Spool valve sections
Coding A 1 (example SLF 5-A 1 L 120/63...)
On the one hand, there is a higher consumer flow with
directional spool valves without an inflow controller (coding A 1)
in comparison with one having a 2-way flow controller (coding
A 2, A 5), as the flow is then directly dependent on the control
pressure of either the connection block‘s 3-way flow controller
(approx. 10 bar) in type PSLF, or the metering valve of a variable
displacement pump (approx. 14 to 20 bar), in type PSVF. On the
other hand, the load-independence is lost, if several consumers
are actuated simultaneously, because the consumer with the
highest load pressure rules the pressure level of the LS-signal
given to the 3-way flow controller and so defines the available
oil flow in the system.
When another valve with lower pressure is actuated now, the flow
can only be regulated by throttling, which means if the highest
load pressure varies, the spool elevation (= throttling) of the
second consumer has to be reset to maintain a constant delivery
flow to the consumer. This consumer flow can be calculated
approx. by (Q
A, B
= expected consumer flow, Q
nom
= rated
consumer flow for a valve with inflow controller coding A 2,
|p
controller
= pressure difference at the flow controller of the
connection block or pump). Q
A, B
, Q
nom
· 0.2 ·|p
controller
Coding A 2 (example SLF 5-A 2 0 63/80)
The standard version of the spool valve comes with load
compensation. Due to the control pressure of the inflow
controller (approx. 6 bar), it regulates a constant flow related
only to the spool elevation, making its delivery independent of
other consumers or system pressure Q , |p
controller
· A
valve spool
Coding A 26 and A 56 (example SLF A-326 J 40/25...)
Symptoms of resonance (audible knocking of the 2-way flow
controllers) can be sometimes caused if pulsating consumers
e.g. radial or axial piston motors with a low number of pistons)
are connected.
This is prevented by use of a restrictor check valve combination
which delays the closing of the inflow controller. This doesn‘t
harm the characteristic of the functional cut-off or the pressure
limiting valves.
Coding A 5 (example SLF 5-A 5 J 160/160)
This version has an increased control pressure enabling high-
er consumer flows (see also above coding A 1 and A 2). The
pressure of the flow controller is 10 bar resulting in a 1.3 higher
flow compared to the standard version (coding A 2).
Coding A 7 (example SLF 5-A 7 H 160/160)
Like coding A 5, due to the necessary pressure drop only in
combination variable displacement pump / constant pressure
system i.e. basically type PSVF.
Coding A 8 (example SLF 3-A 8 L 80/63...)
To ensure max. flow for all subsequent valve sections, the high-
est flow rating (80/... or 160/...) must be selected for the A side
(continuation of P).
Coding AR 2, AR 5 and AR 7
The flow controller acts additionally like a check valve. Thus
preventing a reversal of the flow direction in case of starving
pump delivery.
Coding AA 9 (example SLF 5-AA 9 H 160/160)
Like coding A 5. This version has an increased control pressure
enabling higher consumer flows. Only suited for variable
displacement pump / constant presusre systems i.e. only suited
for PSVF.
The valve body is optimized for higher flow i.e. this controller
cannot be used with standard valve bodies.
6. Appendix
6.1 Notes for selection and lay-out
Dampening screw
acc. to table 2 and 5
Coding
Residual pressure at load induced
pressure of
250 bar 350 bar
S, G, W, B
B 4
B 5
B 6
B 7
125 150
60 70
75 80
85 95
100 120
motors (e.g. fan drives) and features maximum speed in idle
position. The speed can be reduced proportionally down to
dead-halt by energizing the side „b“. The load-independence
is provided when combined with an inflow controller (table 13).
Symbols
Flow pattern symbol P, A, T, Q, K (only size 3)
These spools show positive overlap. Type P overlaps in both
switching directions, i.e. during elevation of the spool the con-
nection P d A(B) is opened before of connection B(A) d R.
This results in an undesired pressure intensification at cylinders
(area ration . 1), therefore we recommend type A, T, Q or K as
these have a one-sided overlapping only. They are intended for
consumers such as hydro-motors / double acting cylinders (area
ratio 1:1) with righting moments / -forces, as well as at cylinders
with drawing loads (area ratio . 1). A short-term preloading
prevents „lowering jolts“ and „running empty“. These valve
spools can substitute load-holding valves to a limited extent. It
should be taken into account, that a short-term working against
the max. system pressure takes place.
The flow coding for A should be selected higher than for B with
spool codings A and T to prevent unintended pressure intensifi-
cations (for spool codings Q and K Q
nom A
< Q
nom B
)
Symbols
D 7700-F page 56
Cylinder area ratio
A
piston
/A
rod
= 1
. 1
Valve spool coding
Piston side
P...
connection A A, T
connection B Q, K
Example
P 40/40
T 25/16
Q 40/63
Symbols Description Application
J, B, R, O Creation of a back
pressure of approx. 20
bar at 1/3 spool lift and
more.
Creation of a back pres-
sure of approx. 100 bar
for up to 1/3 spool lift
I, Y, Z, V
When combined with
over-center valves e.g.
for boom controls
Hydraulic motors (be-
cause of pressure rise
due to area ratio 1:1),
e.g. with cabin slewing
Symbols
I, Y, Z, V
Symbols
J, B, R, O
Symbols
L, M, F, H
Back pressure |p
A(B)-R
WX
Coding acc.
to table 13
2
(1)
5
Q
max A, B
(lpm)
50 120
(67) (150)
67 150
Coding acc.
to table 13
2
(1)
5
Q
max A, B
(lpm)
80
(107)
107
Available versions:
SLF 3-W 50/50
SLF 5-W 120/120
SLF 3-X 80
KQTAP
c) Flow-pattern variations
Flow pattern symbol J, B, R, O and I, Y, Z, V
Oscillations may occur depending on application during start
(e.g. winches) or during normal operation (e.g. crane booms).
They can be caused by the natural frequency of the hydraulic
motors or external load variations e.g. swinging load. The flow
coding (table 15) of the respective spool should correspond to
the cylinder ratio as far as possible.
Flow pattern symbol W
This 4/2-way directional spool valve is intended for applications
where a constant velocity is required e.g. blower or generator
drives. The ability of prop. speed control is restricted, but load
independency is ensured via the inflow controller (table 13).
Flow pattern symbol X
This 2/2-way directional spool valve is intended for hydraulic
I Y Z V
Available versions:
SLF 3 - I 6/6
I 10/10
I 16/16
I 25/25
I 30/30
I 40/40
I 63/63
I 80/80
SLF 3 - V 6/6
V 10/10
V 16/16
V 25/25
V 40/40
V 63/63
V 80/80
SLF 3 - Y 45/45
Y 60/60
SLF 3 - Z 25/25
Z 45/45
Z 60/60
SLF 5 - I 25/25
I 120/120
I 140/140
I 160/160
SLF 5 - Y 150/150
SLF 5 - Z 80/80
SLF 5 - V 25/25
V 120/120
V 140/140
D 7700-F page 57
Flow pattern symbol G
3/3-way directional spool valve for single acting cylinders
Restrictions:
o there is no load signal triggered via the LS-line
o Therefore only usable at open center systems (type PSLF)
and electric actuation with restrictions – idle pump circulation
pressure approx. 11 bar
o The flow while lowering is only throttled (no flow control
functionality) and therefore load-dependent. It is therefore
necessary (safety!) to limit the drop rate by a drop rate braking
valve e.g. type SB acc. to D 6920
o Available version - to symbol G (Q
A
= Q
B
)
SLF 3 - G 3/3 ... G 80/40
SLF 5 - G 160/160
d) Variations for special operation conditions or -requirements
Operation at potentially explosive areas
Electro-hydraulic actuation (type E or EA) version G 24 EX...,
see sect. 3.1.4 table 10 and sect. 4.3
Monitoring of the spool elevation (safety- / switching
function)
With contact- or proximity switch for monitoring the idle position
of the valve spool (suffix to the types A, C, EA, HA, HEA, PA
acc. to sect. 3.2.1 tables 20 and 21 and sect. 4.3)
Maritime ambient climate
The aggressive sea atmosphere requires sufficient corrosion
protection of all moving part of the actuations with hand lever.
The actuation shaft in the hand lever housing is therefore made
of stainless steel as standard. All other parts are either corrosion
inhibiting gas nitrided or made of stainless steel.
Exception: Housing of pneumatic actuation P or PA which is
made of anodized light alloy.
Pressure surges in the return line
Minor leakage may appear at the spring domes of actuations
type AS, CS, E, EAS and E0AS when excessive pressure peaks
(>150 bar) do occur in the return line. This can be prevented
by use of enforcement flanges (suffix G acc. to table 21
in sect. 3.2.1).
Note: The perm. pressure in the return line is limited to approx.
50 bar (see sect. 4.1). The functionality of the actuation
solenoids could be harmed in case of excessive pressure.
e) Use of variable displacement pumps
With Load-sensing controls in alliance with variable displace-
ment pumps, the LS-signal duct for the pump pressure-flow
controller (Load-Sensing metering valve) is relieved, to minimize
circulation losses during idle position (no consumer flow ). This
limiting takes place via the proportional spool valves. Without this
decompression the pump would have to work during no-lift
position with all the remaining flow against the pressure set at the
safety valve of the pressure regulator.
As there exist spool valves without this limiting possibility,
some brands of pressure-flow controllers have a internal
bypass orifice or throttle between LS-signal entrance and
decompressed leakage outlet.
In case of the prop. spool valves type PSVF this is not necessary
and can even cause malfunctions due to lost control oil. The
control oil flow is for functional reasons consciously limited
(approx. 2 lpm) (slow-motion of the consumer).
Note: Care must therefore be taken, to ensure that a possible
bypass orifice in the pressure-flow regulator is plugged!
f) Combination with load-holding valves
It can happen due to exterior variations of load and resonance
that the control system starts to oscillate, if three regulation
devices, the 3-way flow controller in the pump or the connection
block, the 2-way flow controller at the spool valve section plus
load holding insert are connected in series. This can be effectively
suppressed by systematic use of a bypass orifice and throttle-,
check-, pre-load valve combination within the control oil circuit
at the load-holding valve type LHDV acc. to D 7770. A similar
behavior can be achieved with use of the over-center valves
type LHT acc. to D 7918.
g) Combination of more than 12 spool valves
Through the consecutive connection of the LS-signal duct, a
total of max. 12 spool valves can be linked. Whether the spool
valves are arranged in one or more valve banks is irrelevant. This
restriction results from the only limited available oil flow (ensu-
ring slow-motion movements). If more than 12 spool valves in
separated directional spool valve banks are to be coupled via the
LS-signal, a chaining via external shuttle valves is to be used.
i) Indications of actuation HEA
The following notes to the connection of the valve bank have
to be observed to ensure a flawless function of the electric and
hydraulic actuation.
Combination with hydraulic control devices similar
(circuitry acc. to example 1)
Examples 1
Combination with common hydraulic joy-sticks or
hydraulic control devices type FB and KFB acc. to D 6600
and D 6600-01 (circuitry acc. to example 2)
The pressure reducing valves integrated in the joy-sticks open
the consumer line to the tank during idle position. The control oil
flow would escape via this bypass when a valve is simultaneously
solenoid actuated. Therefore it is a must to provide check valves
for the control lines at this kind of circuitry. The same applies to
hydraulic actuations. The used throttles however limit the bypass
leakage. The control oil supply must be dimensioned so that
this leakage can be compensated (> 0.7 lpm per actuated valve
section plus the internal leakage of the hydraulic joy-stick).
Examples 2
j) Optional components
For electro-hydraulic actuations
1. Plugs MSD 3-309 standard, belongs to the scope of
delivery
SVS 296107 Plug with LED‘s for functional
cut-off acc. to sect. 3.2 table 17
(for more details, see D 7163)
2. Electric amplifier EV 22 K2-12(24) acc. to D 7817/1
One board can control two
directional valves.
3. Electric amplifier EV 1 M2 acc. to D 7831/1
EV 1 D acc. to D 7831 D
A remote control potentiometer
with direction switches is required
additionally (see detailed informa-
tion in D 7831/1 sect. 5.2).
4. Logic valve control type PLVC acc. to D 7845 ++
5. Joy-stick type EJ 1, EJ 2 and EJ 3 acc. to D 7844
6. Radio controls are accepted, if they fulfill the requirements of
SK 7814.
(Approved brands:
Co. HBC-ELEKTRONIK in D-74564 Crailsheim,
Co. HETRONIK Steuer-Systeme in D-84085 Langquaid,
Co. NBB-Nachrichtentechnik in D-75248 Ölbronn-Dürrn,
Co. SCANRECO Industrieelektronik AB, Box 19144,
S-5227 Södertälje)
Load-holding valves
Load-holding valves type LHT acc. to D 7918 or type LHDV acc.
to D 7770 and note sect. 6.1 f, type LHK acc. to D 7100 only with
„very stiff“ systems and directional spool valves without inflow
controller (coding 1 acc. to table 15, sect. 3.2.1)
Other valves
Proportional spool valve type PSL(V) size 2 acc. to D 7700-2
(can be combined via intermediate plate ZPL 32 with size 3)
Proportional spool valve type PSL(V) size 3 acc. to D 7700-3
(can be combined via intermediate plate ZPL 32 with size 2 or via
intermediate plate ZPL 53 with size 5)
Proportional spool valve type PSL(V) size 5 acc. to D 7700-5
(can be combined via intermediate plate ZPL 53 with size 3 and
via intermediate plate ZPL 52 with size 2)
Proportional pressure reducing valve type PMZ acc. to D 7625
Hydraulic joy-stick type KFB01 acc. to D 6600-01
D 7700-F page 58
2b)
2a)
D 7700-F page 59
6.2 Example circuit
Control system with PSVF, and variable displacement pump
PSVF A1/380/4 - 3 - A2 J 40/40 A200 B200 /E /3 AN210 BN210
- A2 J 80/40 A280 B130 /E /3 AN290 BN140
- A2 J 25/16 /EA /3
- E1 - G 24
Flow pattern symbol
acc. to the order
example
All installation, set-up, maintenance and repairs must be
performed by authorized and trained staff.
The use of this product beyond the specified performance
limits, use of non specified fluids and/or use of not genuine
spares will cause the expiration of the guarantee.
6.3.1 Mounting
The mounting of the valve bank must be performed in such
a way that no stress is induced.
Three screws and elastic washers between valve assembly
and frame are recommended for fastening.
6.3.2 Piping
All fittings used must utilize deformable seal materials.
Do not exceed the specified torque!
6.3.3 Notes for converting the inlet section type PSL(V)F A../..-5
The inlet section type PSLF A../..-5 can be converted any
time into a connection block for variable displacement pump
systems (correct type now PSVF AS../..-5) and vice versa.
This requires replacing the parts listed below.
Attention: The screw (part No. 6380 013)
D or carburetor
jet M4x0.6 are secured with liquid screw lock,
which must be applied again during reinstalla-
tion of these parts.
When converting type PSVF..-5 into
PSLF..-5 an additional damping screw S
(part No. 7778 301) E is required.
6.3 Notes regarding assembly, installation and
conversion
Type PSVF A../..-5
D
Carburetor
jet Ø 0.6
o E With type
PSVF AS..-5
o Tapped plug
(7778 036) with
type PSVF A..-5
(standard)
o Screw
(7778 062) with
type PSVF AB..-5
Type PSLF A../..-5
open
D
E With
type PSLF..
(standard)
E
D 7700-F page 60
6.3.5 Seal kits
Size 3 Size 5
Inlet section DS 7700-F 31 DS 7700-F 51
Valve section DS 7700-F 32 DS 7700-F 52
Sub-plate DS 7700-F 34 DS 7700-F 54
Control
groove
Tapped
plug
6.3.4 Notes on changing the spool
The valve spools are not mated to one spool housing.
Therefore valve spools can be changed at any time to adapt
to changing consumer consumption.
The following routine is to be followed particularly:
Advice on changing the valve spool
1. Slacken screws ; (ISO 4762-M5x8-8.8-A2K), remove
spring cover
2. Remove screw < (M 6x40, machined flat head screw
drawing No. 7709 042)
3. Remove spring assembly including spring cap =
4. Slacken screws > (ISO 4762-M5x50-8.8-A2K)
5. Lift lever housing including spool out of spool housing,
drawing ? @
6. Remove circlip DIN 6799 3,2 and remove bolt A B
7. Assemble with (new) spool in reverse sequence
Attention: The control grooves of the valve spool should
always be installed towards the end plate!
Exception: Valve spools with flow coding 80
(size 3) and 160 (size 5) do not show
control grooves.
Indications for angling the lever housing by 180°
(inversion of the shifting mode)
As set out in 1. - 7. above, however instead of a new
valve spool the existing one has to be disconnected, angled
at 180° and remounted (see above mentioned note). The
intermediate plate C together with the lever housing, have
to be angled at 180°.
All lever housings of the valve bank have to be rotated!
Lever housing
angled at 180°